Honeywell TR71 Manuale Utente

Pagina di 24
ZIO
®
/ZIO PLUS LCD WALL MODULES
3
63-2719—03
SETUP AND CONFIGURATION
Initial Setup and Configuration
Once the wall module is wired to the controller, you configure 
the wall module using the PC-based, Niagara Workbench 
Tool. Refer to the applicable programmable controller User’s 
Guide. (Refer to the Honeywell Spyder User’s Guide, form 63-
2662, or the ComfortPoint Programmable Controller User’s 
Guide, form 63-2663, depending on the programmable 
controller used.) This tool is used to configure the wall module 
for either the Spyder or the ComfortPoint programmable 
controller.
Confirm Bus Address Setting
Check to ensure that the Wall Module’s bus address dial 
(located on the back of the module) is set to match the setting 
in the configuration tool. TR70 models can be set from 1–5 
and TR71/TR75 can be set from 1–10 (0 on the Zio address 
dial is equal to 10 in the configuration tool). The address must 
be different for each device on the Sylk bus. Up to four Zios 
per Spyder are allowed with any combination of TR71/TR75s 
and up to three Zios are allowed if one or more is a TR70 
model.
Selecting the Wall Module
You will use the Sylk S-Bus wall module function block from 
the Palette’s Built-In folder (see Fig. 3). This configuration has 
nothing programmed except the room temperature parameter 
and occupancy status.
1. Add the Sylk S-Bus Wall Module function block to the 
wire sheet via a left click, drag, and drop. See callout 1 
2. Right click on the S-Bus Wall Module function block to 
open the Configuration Properties menu. See callout 2 
3. Left click on the title, Configuration Properties. This 
action starts the Configuration Wizard. The Configura-
tion Wizard steps (see Fig. 5 on page 4) are used to 
configure the wall module.
Fig. 3. Niagara Tool Interface - S-Bus wall module selection.
TR71/TR75 Labels
The TR71/TR75 allows the use of the following special 
characters in label fields such as Categories and Parameter 
Names: underscore ( _ ) to insert a space, hyphen ( - ), and 
forward slash ( / ). The TR70 allows use of the underscore 
( _ ) character to insert a space.
Navigation and Memory Usage
The Honeywell Spyder Tool uses an intuitive, window-based 
interface. A Help button on each screen provides assistance 
with any entry or process.
IMPORTANT
Use the Help button to display context specific help 
for the current window or pane display. See the lower 
left corner of Fig. 6 on page 5 for the location of the 
Help button.
NOTE: At any time, clicking the Preview button (lower left of 
main window, see Fig. 6 on page 5) displays the 
updated wall module LCD as a pop-up. Preview sim-
ulates the actual wall module interface and allows 
you to verify the operation of the current configura-
tion of the wall module. See “Preview” on page 16.
Navigation
Table 3 describes the navigation buttons at the bottom of the 
wall module window. See the bottom of Fig. 7 on page 5 for 
the location of these buttons. Buttons are greyed when 
unavailable.
VAV_Temp_NoBal_NwOvrdTime
VAV_Temp_MnMxBal_NwOvrdTime
VAV_Temp_KfacBal_NwOvrdTime
VAV_Temp_NoBal_AllOverride
SBusWallModule
M27820
RIGHT CLICK
DRAG
AND
DROP
1
2
Table 3. Navigation Buttons.
Item
Function/Use
Help
When clicked, this button provides context sensitive 
help for the currently selected item or parameter.
Preview When clicked, this button displays the updated wall 
module LCD in a pop-up window pane. Preview is 
fully interactive and simulates the actual wall 
module interface as currently configured (see 
Save to 
Library
For new custom configurations and standard 
configurations. 
Clicking the button opens the Save to Library 
screen (shown in Fig. 25 on page 17). This action 
allows you to save the entire current wall module 
configuration.
The Save to Library button is disabled until you 
change the configuration (application). After a 
change is made, you can save the new 
configuration into the library under a new name.
Back
Takes you backward one step in the wizard 
interface.
Next
Takes you forward one step in the wizard interface.
Finish 
Clicking this button commits all changes to the 
database, closes the Configuration Wizard, and 
returns you to the wire sheet. 
Cancel
Prompts you with a confirmation message.
If you reply Yes, then all selections/entries made 
since the Save to Library button or Finish button 
was last pressed are ignored, and the wizard 
interface quits.