Honeywell L6007 Manuale Utente

Pagina di 20
L4006,7,8; L6006,7,8 AQUASTAT
®
 CONTROLLERS
7
60-2104—10
Table 2. L6006, L6007, L6008 Controller (SPDT Switching) Specifications.
Model
Application
Range 
°F (°C)
Midscale 
Differential 
°F (°C)
Insertion
a
Available Options
L6006A
Circulator and low 
limit or high limit
100° F to 240° F 
(38° C to 116° C) 
or 
100° F to 290° F
(38° C to 143° C)
5° F (3° C) fixed 
or 
5° F to 30° F 
(3° C to 17° C) 
adjustable
Horizontal
— SUPER TRADELINE model 
available.
— Modified dial with stop.
— NPT brass spud 1/2 in. or 3/4 
in. (13 mm to 19 mm)
— 3-3/8 in. (86 mm) insertion.
— Without well.
— Adapter for horizontal or 
vertical mount.
— Insulation depth 1-1/2 in. or 
3 in. (38 mm or 76 mm).
L6006B
Circulator and low 
limit or high limit
100° F to 240° F 
(38° C to 116° C)
5° F (3° C) fixed 
or 
5° F to 30° F 
(3° C to 17° C) 
adjustable, or 
30° F (17° C) 
fixed.
Horizontal
— Direct immersion.
— Insulation depth 1-1/2 in. 
(38 mm).
— 3/4 in. (19 mm ) brass 
compression fitting.
L6006C
Circulator, low limit, 
and high limit
65° F to 200° F 
(18° C to 93° C)
5° F (3° C) fixed 
or 
5° F to 30° F 
(3° C to 17° C) 
adjustable
Horizontal or 
vertical surface 
mounted
— TRADELINE model available.
— Strap-on, surface mount.
L6007A
Circulator and low 
limit or high limit
40° F to 180° F 
(4° C to 82° C)
Fixed
Horizontal or 
vertical
— Insulation depth 1-1/2 in. or 3 
in. (38 mm or 76 mm).
L6008A
Circulator and low 
limit cooling
100° F to 240° F 
(38° C to 116° C) 
or 
-30° F to +70° F 
(-35° C to +21° C)
5° F (3° C) fixed 
or 
5° F to 30° F 
(3° C to 17° C) 
adjustable
Remote bulb
— TRADELINE models 
available.
— Modified dial with stop.
— Capillary 5-1/2 ft (1.7 m).
L6008G
Two-stage Aquastat 
Controller to cycle 
two-stage gas 
valve.
130° F to 230° F 
(54° C to 110° C) or 
60° F to 160° F (16° 
C to 71° C)
3-1/2° F (2° C) 
fixed
Remote bulb
— Capillary 6 ft (1.8 m).
— Adjustable interstage 
differential; 5° F to 10° F 
(2° C to 6° C).
L6008H 
(maximum 
temperature 
of element 
405° F 
(207° C))
Low fire Aquastat 
Controller
150° F to 200° F 
(66° C to 93° C)
15° F (8° C) 
fixed
Remote bulb
— Capillary 33 in. (0.8 m).
a
 Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. NPT and 