Honeywell 95-7769-01 Manuale Utente

Pagina di 176
WEBVISION™
153
95-7769—01
Table 89. NXVFD Application of Points.
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values
Adjust Input / Actual Value 2
X
X
X
X
 Units=%
 Precision=1
 Min.=-163.8
 Max=163.8
Clear Counter
X
X
X
X
 Units=%
 Precision=1
 Min=0.0
 Max=100.0
Drive Speed Setpoint
X
X
X
X
 Units=%
 Precision=1
 Min=0.0
 Max=100.0
Free Analog / Input Actual Value 1
X
X
X
X
 Units=%
 Precision=1
 Min.=-163.8
 Max=163.8
Reset Fault
X
X
X
X
 Units=%
 Precision=1
 Min=0.0
 Max=100.0
Torque Reference / Reference for PID
X
X
X
X
 Units=%
 Precision=1
 Min.=-163.8
 Max=163.8
AC Fault Code
X
X
X
 Units=%
 Precision=1
 Min.=-163.8
 Max=163.8
Fault Active
X
X
X
 True or False
DC Link Voltage
X
X
X
 Units=%
 Precision=1
 Min=-163.8
 Max=163.8
Drive Current
X
X
X
 Units=A
 Precision=1
 Min=-3276.8
 Max=3276.7
Drive Energy
X
X
X
 Units=kW/hr
 Precision=0
 Min=0.0
 Max=65535.0
Drive Power
X
X
X
 Units=kW
 Precision=1
 Min=0.0
 Max=6553.5
Ready
X
X
X
 True or False
Running
X
X
X
 True or False
Drive Speed
X
X
X
 Units=%
 Precision=1
 Min=-163.8
 Max=163.8
Active Fault Code
X
X
X
 Units=null
 Precision=0
 Min=0.0
 Max=65535.0