SYSTEM COMMISSIONING CHECKLIST
5
Use the following checklist during commissioning to 
assure all Setpoints have been programmed to the desired 
value and all calibrations have been performed. The 
Setpoints are grouped under the Display Screen in which 
they appear. The indented screens are subscreens of the 
numbered screens and are accessed from the numbered 
screens. An explanation of each setpoint or Calibration 
Procedure below is contained in the reference document 
listed in parenthesis adjacent to each item. If any of 
the  Setpoints  have  to  be  changed,  use  the  standard 
programming  procedures  in  the  Operation  Section. 
Thresholds, values and calibrations of items marked with 
an asterisk “*” have been determined and entered/set at 
the YORK Factory at the time of manufacture. 
1. PROGRAM JUMPERS/SWITCHES
     ____ Verify  Microboard  Program  Jumpers  and 
Program Switches are configured appropriately. 
2. SETPOINTS Screen:
The setpoints listed on the SETPOINTS Screen have 
already been programmed at the chiller/condensing unit. 
The values shown reflect the previously programmed 
values. However, the setpoints listed here can be changed 
on this screen if desired only if the chiller/condensing 
unit  is  in  remote  conrol  mode. This screen is used 
primarily as a central location from which most setpoints 
can be programmed. If it is not desired to change any 
of the listed setpoints, proceed to the following RCC 
SETPOINTS Screen.   
3. RCC SETPOINTS Screen:
     ____ Number of Units Connected
RCC SETUP Screen
     ____ Enable Clock            
     ____ Enter CLOCK Time and Date  
     ____ Select 12 or 24 hour display mode              
COMMS Screen:          
Enter the following parameters as required for com-
munication to the remote chiller panel(s):
     ____ RCC Poll Time
PRINTER Screen:                 
If  Printer  is  connected  to  Microboard  serial  ports, 
enter the following: 
     ____ Baud rate
     ____ Number of data bits 
     ____ Number of stop bits
     ____ Parity 
     ____ Automatic printer logging Enable/disable
     ____ Log start time
     ____ Log output interval
     ____ Log Unit Selected (1-8, All)
     ____ Printer type