OVERVIEW
This screen is accessed from the UNIT screen. As many 
as six Operator selected parameters can be plotted in 
an  X/Y  graph  format. The  X-Axis  is  scaled  per  the 
selected  Data  Collection  Interval  and  displayed  in  a 
time of day or elapsed time format, as selected with 
the X-axis toggle key. The Y-Axis is scaled for each 
parameter  per  the  selected  minimum  and  maximum 
value for each parameter. Analog parameters are scaled 
in  pressure,  temperature,  volts,  amps,  hertz  or  time. 
Digital on/off parameters are scaled as zero (off) and 
one (on). Only one Y-Axis label is displayed at a time. 
The Y-Axis Toggle Key is used to toggle the Y-Axis 
labels  through  the  different  parameters. The Y-Axis 
label that is being displayed is identified at the top of the 
graph. All parameters are displayed simultaneously. For 
identification,  each  plotted  parameter  and  associated 
Y-Axis labeling is color coordinated.
The  parameters  are  sampled  at  the  selected  Data 
Collection Interval and plotted using 450 data points 
across the X-Axis. If the actual value of the sampled 
parameter is less than the Y-Axis label minimum for 
that parameter, the value will be plotted at the minimum 
value. Similarly, if the actual value is greater than the 
Y-Axis label maximum for that parameter, the value 
will be plotted at the maximum value.
There are two types of charts that can be created: ONE 
SCREEN or CONTINUOUS. When the plotting has 
reached the end of the X-Axis, one of the following 
will  occur,  depending  on  which  is  selected:  If  ONE 
SCREEN has been selected, the trending stops and the 
data  is frozen.  If CONTINUOUS  has  been  selected, 
the oldest data is dropped from the left-hand side of the 
graph at the next Data Collection Interval. Thereafter, 
the oldest data is dropped from left-hand side of the 
graph at each Data Collection Interval.
Only parameters from the selected Unit are trended. 
The same parameters that have been selected for a Unit, 
will be selected by default for the next selected Unit. 
When on the Home screen, a Unit is not selected and 
any trending is stopped. Trending is also stopped if a 
power failure occurs while it is running. After trending 
is stopped, the last screen of data that was collected will 
be displayed on the trending screen and the START key 
must be pressed to initiate a new trend screen. 
DISPLAY ONLY
This  screen  allows  the  user  to  view  the  graphical 
trending  of  the  selected  parameters  and  is  also  a 
gateway to the graph setup screens. 
TRENDING SCREEN
FIG. 15 TRENDING
00574VIPC
Operation