York 00497VIP Manuale Utente

Pagina di 112
YORK INTERNATIONAL
40
OVERVIEW
This  screen  is  accessed  from  the  Trending  screen. 
This screen is used to configure the trending screen. 
The  parameters  to  be  trended  are  selected  from  the 
Common Slots Screen or Common Slots Master list 
and entered as Slot Numbers for Data Points 1 through 
6. The Y-Axis minimum and maximum values for each 
parameter are entered as Data Point Min and Data Point 
Max for Data Points 1 through 6. The interval at which 
all the parameters are sampled is selected as the Data 
Collection Interval.
DISPLAY ONLY
None
PROGRAMMABLE
Chart Type
Selects either CONTINUOUS or ONE SCREEN type 
of graph.
Collection Interval
Selects the interval at which the parameters are sampled. 
There are 450 data points displayed across the X-Axis 
of the graph. Each point represents the instantaneous 
value  of  the  parameter.  The  user  selects  the  time 
interval between these points. This is called the DATA 
COLLECTION INTERVAL, or the interval at which 
the parameter is sampled. This interval is programmable 
over the range of 1 second to 3600 seconds (1 hour), in 
one second increments. The selected interval not only 
determines the sample interval, but also the full screen 
time display. The full screen time display is a result 
of the selected interval in seconds, multiplied by the 450 
data points. For example, if the Data Collection Interval 
is programmed for 900 seconds, the parameter would 
be sampled every 900 seconds, with the last 112.5 hours 
(4.7 days) of data viewable on the screen. Therefore, the 
selected interval is a compromise between resolution 
and full screen time display. Select the desired Data 
Collection Interval as follows:
 1. Determine the desired time interval (in seconds), 
between data samples. 
    
 2. Calculate the full screen time display as follows:
    •  450  x  Data  Collection  Interval  =  full  screen 
 
seconds
    •  full screen seconds / 60 = full screen minutes
    •  full screen minutes / 60 = full screen hours
    •  full screen hours / 24 = full screen days
 
 3. Decide  if  the  resultant  sample  interval  and  full 
screen display meet the requirements. If not, select 
a different sample interval.
TREND SETUP SCREEN
FIG. 16 TREND SETUP
00575VIPC
Operation