York 00497VIP Manuale Utente

Pagina di 112
YORK INTERNATIONAL
46
SETPOINTS SCREEN
Operation
OVERVIEW
 
This screen, accessed from the Unit screen, provides a 
convenient location for programming the most common 
setpoints involved in the chiller/condensing unit control. 
The setpoints depend on the type of unit.
Values  on  this  screen  are  only  pro-
grammable if the chiller/condensing 
unit is in remote control mode. These 
values are only viewable if the unit is 
in local mode.
DISPLAY ONLY
None
 
PROGRAMMABLE
Leaving Chilled Liquid Temperature or
Return  Chilled  Liquid Temperature  or  Suction 
Pressure or Discharge Air Temperature Setpoint
This value allows the user to define the cooling setpoint 
that is to be maintained by the chiller/condensing unit. 
See the unit’s Installation, Operation and Maintenance 
Manual (IOM) for it’s programmable range. 
Leaving  Chilled  Liquid Temperature  or  Return 
Chilled Liquid Temperature or Suction Pressure or 
Discharge Air Temperature - Control Range 
This is the maximum allowable positive and negative 
deviation that is acceptable from setpoint in the system 
application. See the unit’s Installation, Operation and 
Maintenance  Manual  (IOM)  for  it’s  programmable 
range. 
Remote Chiller Run or Remote Unit Run
The chiller/condensing unit can be selected to either 
Run  or  Stop.  Selecting  Stop  will  command  the 
chiller/condensing unit to shut down. Selecting Run 
will allow the chiller/condensing unit to turn on. 
Current Limit Setpoint
This is the motor current limiting setpoint. The chiller 
will be limited from loading when the motor current 
equals or exceeds this value. Typically, for most instal-
lations,  no  limiting  is  required  and  the  programmed 
limiting will be set at or above 100%. 
Load Limit Setpoint (YCAL Chillers)
Load Limiting can be programmed from 0 to 2. 
  Load Limit 0 = no load limit
  Load Limit 1 = 50% load limit - 2/4 compressor units.
  Load Limit 1 = 66% load limit - 3/6 compressor units.
  Load Limit 2 = 33 % - 3/6 compressor units only.
Change Schedule
The  daily  schedule  is  a  1  week  schedule  and  must 
be  programmed  for  the  start  and  stop  time  for  each 
week day and a holiday if desired. A box is provided to 
specify which days are to use the holiday schedule.  
Programming the same time for both 
Start  and  Stop  times  will  cause  the 
display to enter 00.00 for both times 
which will cause the chiller to always 
be allowed to run.
Repeat Monday
The other days can be selected to change to the Monday 
schedule. 
Clear Schedule
In  a  situation  where  it  is  required  to  run  the  chiller 
24  hours  a  day,  7  days  a  week,  the  Chiller  Control 
panel should first have its entire Daily Schedule zeroed 
(00.00) for all Start and Stop times. This puts the chiller 
in  the  run  mode  at  all  times. The  OptiView  Remote 
Control  Center  may  now  be  programmed  with  all 
zeroes (00.00) for all Start and Stop times by pressing 
the Clear Schedule button. Since the chiller panel is 
already in the run mode, programming the OptiView 
Remote  Control  Center  for  all  zeroes  will  keep  the 
chiller in this mode indefinitely, allowing the chiller to 
run whenever demand requires.
NAVIGATION
Home
Causes an instant return to the Home Screen.
Unit Data
Causes an instant return to the Unit Screen.