YORK INTERNATIONAL
60
PRINTERS
A printer can be connected to the OptiView Remote 
Control  Center’s  Microboard  to  print  the  following 
reports. The  screen  from  which  each  report  can  be 
generated is listed in parenthesis.
  •  Operating  Data  -  Present  system  parameters 
(Unit)
  •  History  -  System  parameters  at  the  time  of  the 
last  fault  while  running  and  last  saved  faults 
(History)
The printer can be permanently connected to the Remote 
Control Center or connected as required to produce a 
report. If permanently connected, a DATA LOGGING 
feature  can  produce  a  Status  report  automatically, 
beginning at an Operator selected start time and occurring 
at an Operator selected interval thereafter.
The  following  figures  are  examples  of  the  different 
print reports. 
  •  Figure 28 - Operating Data
  •  Figure 29 - History (Header)
PRINTERS
The following Printers can be used. Printers must be 
equipped with an RS-232 Serial interface.
  •  Okidata 
    Models: 182,182 turbo, 184 turbo
    Dimensions: 14 in. wide x 10.5 in. deep 
    Paper: 8.5 in. wide 
    Type: Dot matrix impact 
   
  •  Weigh-Tronix – 
    Models: 2600, 1220 
    Dimensions: 2.3 in. wide x 2.8 in. deep 
    Paper: 2.25 in. wide 
    Type: Dot matrix impact
   
  •  Seiko –
    Model:  DPU414-30B  (Power  supply  PW4007-U 
I required)
    Dimensions: 6.3 in. wide x 6.7 in. deep
    Paper: 4.4 in. wide
    Type: Thermal
    Purchase:   Contact your local
     
 
YORK Service Office
The  OptiView  Remote  Control  Center  provides  the 
required formatting control codes for the printers above 
when the printer is selected on the PRINTER Screen 
in the instructions below. These codes are transmitted 
through the serial interface to the printer to provide a 
proper print format. Different printers require different 
formatting control codes. Other printers might provide 
proper  operation  when  connected  to  the  OptiView 
Remote  Control  Center.  However,  the  print  format 
may not be correct or as desired. Proceed with caution 
and use the following guidelines if an unlisted printer 
is selected:
 1. All must be capable of RS-232 Serial communications.
 2. Primary  differences  between  printers  involve  the 
formatting  control  codes  required  by  the  printer. 
These  codes  are  sent  from  the  Control  Center  to 
the  printer.  For  example, Weigh-Tronix  printers 
require a control code to select 40 column width. 
This same code is interpreted by the Okidata printer 
as an instruction to print wide characters. In some 
instances,  a  printer  will  ignore  a  code  it  cannot 
interpret.
 3. The  OptiView  Remote  Control  Center  requires 
a  busy  signal  from  the  printer  when  the  printer 
receive  buffer  is  full. This  causes  the  OptiView 
Remote Control Center to momentarily terminate 
data transmission until the printer can accept more 
data. The  busy  signal  polarity  must  be  asserted 
low when busy.
PRINTER CONNECTIONS
Connect the printers to the Control Center Microboard as 
follows. Only one printer can be connected at a time.
• OKIDATA 182, 182 turbo, 184 turbo
  
Microboard       Printer                     Function
         J2-4                pin 3                Tx (data to printer)
         J2-2               pin 11     DSR (busy signal from printer)
         J2-9                pin 7                           Gnd
      Cabinet                                               shield
• WEIGH-TRONIX
  Microboard       Printer                     Function
         J2-4                pin 2                Tx (data to printer)
         J2-2                pin 5      DSR (busy signal from printer)
         J2-9                pin 7                           Gnd
      Cabinet                                               shield
Printers