SYSTEM ARCHITECTURE
(REFER TO FIG. 28)
The OptiView Remote Control Center (RCC) performs 
the following functions:
  •  Displays  chiller  operating  conditions,  alarms, 
shutdown messages and history data. 
  •  Accepts operator-programmed setpoints.
  •  Provides chiller operating data and status to remote 
devices via serial communications. 
  •  Allows real-time data and history data to be printed 
on an optional printer.
The  RCC  is  a  microprocessor  based  control  system 
that receives analog and serial data inputs and controls 
serial  data  outputs  per  instructions  in  the  operating 
program. A panel mounted display and touch-sensitive 
keypad permit remote operation. 
In  some  applications,  overall  system  temperatures 
are sensed by thermistors connected to the Remote 
Control  Center. The  output  of  each  thermistor  is  a 
DC voltage that is analogous to the temperature it is 
sensing. Typical  output  voltage  range  of  both  is  0.5 
to  4.5VDC. These  are  analog  inputs  to  the  Remote 
Control Center.
Serial Data is transmitted to and received from devices 
in RS-232, RS-485 and TX/RX (opto-couple) form. 
All  OptiView  Remote  Control  Centers  contain  the 
following standard components:
  •  Microboard
  •  Keypad
  •  Display
  •  Power Supply
Figure 33 is a Remote Control Center block diagram 
of the standard components.
The microprocessor and all supporting logic circuits, 
along with the memory devices containing the operating 
program, reside on the Microboard. All remote control 
decisions are made here. In some applications it receives 
analog  inputs  from  devices.  The  analog  inputs  are 
connected directly to the Microboard. 
A front panel-mounted Keypad allows Operator and 
Service Technician user interface. Membrane keys are 
used  to  display  chiller  and  system  parameters,  enter 
setpoints  and  perform  chiller  and  Remote  Control 
Center diagnostics. 
A front panel mounted liquid crystal Display allows 
graphic animated display of the connected chiller units, 
chiller  unit  subsystems  and  system  parameters. The 
chiller  and  working  components  of  the  chiller  are 
displayed, along with chiller operating pressures and 
temperatures. The  Keypad  is  used  to  select  displays 
showing increasing levels of detail of chiller working 
components. 
A self-contained Power Supply supplies the necessary 
DC voltages for all the components within the Remote 
Control Center. 
Serial  data  interface  to  the YORK  ISN  Building 
Automation System is through the J12 connector. 
Service