York 00497VIP Manuale Utente

Pagina di 112
FORM 50.40-OM2
9
YORK INTERNATIONAL
CHILLER/CONDENSING CONTROL PANEL(S)
All communication with the chiller/condensing units 
will occur over a single RS-485 port. Reference Figure 
2 and the Installation instructions. 
When  the  OptiView  RCC  is  first  turned  on  it  will 
initialize by requesting current data and history buffer 
information from the units connected. After the history 
buffers are filled, only current data will be continuously 
requested. Every eight hours the OptiView RCC will re-
initialize. If the control panel updates the history buffer 
(a  safety  shutdown  has  occurred),  the  control  panel 
will  send  the  chiller  shutdown  data  to  the  OptiView 
RCC  upon  receipt  of  the  next  valid  OptiView  RCC 
transmission. The OptiView RCC will recognize that 
a safety shutdown has occurred by the Update History 
Buffer bit being set. If this bit is ever 1, the data dump is 
assumed to be a shutdown data dump and the OptiView 
RCC will update its history buffers with the new data 
and start a printout of the transmitted data through its 
RS232 port. If the OptiView RCC had been requesting 
another type of data dump (i.e. a daily schedule dump), 
the OptiView RCC will repeat its request on the next 
transmission.
While  at  the  Home  Screen,  the  OptiView  RCC  will 
communicate with each unit in order. Once a unit has 
been selected by entering the Unit Screen or any screen 
below it, that unit will be polled between every unit 
in order. This will allow the selected unit to update its 
information quickly while still maintaining information 
for the Home Screen.
A command string is used to indicate what data the 
OptiView RCC is requesting and to modify control data 
in the chiller control panel. If the chiller/condensing 
unit  is  in  remote  control  mode  then  its  Local  Set 
Point,  Local  Range,  Daily  Schedule,  Holiday,  Start 
/  Stop  Command,  and  Current  /  Load  Limit  can  be 
programmed from the OptiView RCC. The OptiView 
RCC will send a command string once any of these are 
modified at the OptiView RCC. If the OptiView RCC 
sends a Stop command, the chiller/condensing unit will 
turn off. If the OptiView RCC sends a start command, 
the chiller/condensing unit will be allowed to run if all 
the other run requirements of the unit are made.
A  chiller/condensing  unit  that  is  in  remote  control 
mode will use local control (set points and start / stop 
information),  if  a  valid  transmission  has  not  been 
received for 5 minutes from the OptiView RCC. The 
remote  commands  will  be  used  again  once  a  valid 
new transmission has been processed. The OptiView 
RCC  will  display  an  error  message  indicating  the 
communications  problem  when  such  a  condition 
occurs.
A  general  status  message  for  each  unit  is  displayed 
on  the  Home  Screen. The  messages  displayed  will 
include  communications  status.  Not  Initialized  will 
be  displayed  upon  power-up  for  all  units  until  the 
OptiView RCC begins to poll and receive data from 
that  unit.  Initializing…  will  be  displayed  while  the 
OptiView RCC is polling a unit for all current, schedule, 
and history data the first time after power-up. Loss of 
Comms will be displayed after 5 minutes have elapsed 
with no response from a previously initialized unit. If 
any of these messages is displayed, the unit’s button 
will be disabled not allowing it to be selected.
The Control Center Microboard (J12) communicates 
with this board via a 0/+5VDC serial data communica-
tions link. If this communications link does not operate 
properly, correct Microboard J12 serial port operation 
can  be  verified  using  the  Serial  Inputs  and  Outputs 
diagnostic procedure in the “Service” section of this 
book.