The problems that could be encountered in the Control 
Center are in the following categories:
 
• Keypad
 
• Display
 
• Serial Input/Output (I/O)
 
• Digital Input/Output (I/O)
 
• Analog Inputs
There is a Diagnostic and associated Troubleshooting 
procedure  for  each  category.  They  are  described 
on  the  following  pages. The  offline  diagnostics  are 
accessed from the Diagnostics Main Screen, which is 
entered using the procedure below. If there is a Remote 
Control  Center  problem,  determine  the  category  of 
the problem. Then perform the applicable Diagnostic. 
If the Diagnostic reveals a malfunction, perform the 
Troubleshooting  procedure  to  locate  the  defective 
component.
There are several documents that must be referred to 
while performing the Diagnostics and Troubleshooting 
procedures. Each procedure references the Section and 
figures of this book that describe the operation of the 
component being tested. 
The  Offline  diagnostic  screens  are  only  available 
when the panel is powered on (or rebooted) with the 
Diagnostics Enable dip switch in the Enabled position. 
When  in  this  mode  all  normal  RCC  functions  are 
disabled. If the Diagnostics Enable dip switch is placed 
in the Disabled position while the panel is in the Offline 
Diagnostics mode, the Diagnostics task will cause the 
panel to reboot into the online diagnostics mode.
OFFLINE DIAGNOSTICS & TROUBLESHOOTING
(REFER TO FIG 48 & 49)
Service