Bradford-White Corp 07.05.228.00 Manuale Utente

Pagina di 28
Model
kW
Volts
Phase
Amp Draw
Breaker or
Copper
Conduit
L1
L2
L3
Fuse Size
Wire Size
Size
LI663CFC
6
208
1
29
29
-
40
8
1/2" (13 mm)
LI663CFD
6
208
3
14
25
14
40
8
1/2" (13 mm)
LI663CFE
6
240
1
25
25
-
40
8
1/2" (13 mm)
LI663CFF
6
240
3
13
22
13
30
10
1/2" (13 mm)
LI663CFM
6
480
3
6
11
6
15
14
1/2" (13 mm)
LI693CFC
9
208
1
43
43
-
60
6
1/2" (13 mm)
LI693CFD
9
208
3
22
38
22
50
8
1/2" (13 mm)
LI693CFE
9
240
1
38
38
-
50
8
1/2" (13 mm)
LI693CFF
9
240
3
19
33
19
50
8
1/2" (13 mm)
LI693CFM
9
480
3
9
16
9
20
12
1/2" (13 mm)
LI6123CFC
12
208
1
58
58
-
90
3
1" (25 mm)
LI6123CFD
12
208
3
33
33
33
50
8
1/2" (13 mm)
LI6123CFE
12
240
1
50
50
-
70
6
1/2" (13 mm)
LI6123CFF
12
240
3
29
29
29
40
8
1/2" (13 mm)
LI6123CFM
12
480
3
14.5
14.5
14.5
20
12
1/2" (13 mm)
LI6153CFC
15
208
1
72
72
-
90
3
1" (25 mm)
LI6153CFD
15
208
3
41.7
41.7
41.7
60
6
3/4" (19 mm)
LI6153CFE
15
240
1
62.5
62.5
-
90
3
1" (25 mm)
LI6153CFF
15
240
3
36.1
36.1
36.1
50
8
1/2" (13 mm)
LI6153CFM
15
480
3
18.1
18.1
18.1
30
10
1/2" (13 mm)
LI6183CFC
18
208
1
86.5
86.5
-
125
1
1-1/4" (32 mm)
LI6183CFE
18
240
1
75
75
-
100
3
1" (25 mm)
LI6183CFF
18
240
3
43.4
43.4
43.4
60
6
3/4" (19 mm)
LI6183CFM
18
480
3
21.7
21.7
21.7
30
10
1/2" (13 mm)
LI6243CFC
24
208
1
115.4
115.4
-
150
1/0
1-1/4" (32 mm)
LI6243CFD
24
208
3
66.7
66.7
66.7
90
3
1" (25 mm)
LI6243CFE
24
240
1
100
100
-
125
1
1-1/4" (32 mm)
LI6243CFF
24
240
3
57.8
57.8
57.8
90
3
1-1/4" (32 mm)
LI6243CFM
24
480
3
29.9
29.9
29.9
40
8
1/2" (13 mm)
LI6303CFC
30
208
1
144
144
-
200
3/0
1-1/2" (38 mm)
LI6303CFD
30
208
3
83.3
83.3
83.3
125
1
1-1/4" (32 mm)
LI6303CFE
30
240
1
125
125
-
175
2/0
1-1/2" (38 mm)
LI6303CFF
30
240
3
72.3
72.3
72.3
100
3
1" (25 mm)
LI6303CFM
30
480
3
36
36
36
50
8
1/2" (13 mm)
SPECIFICATIONS
Form No. EBOOSTERBWM-1009
4
Circuit Breaker and Fused Disconnect Switch Sizes — 6 to 30 kW
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to
be mounted remote and wired by contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based on conductors
plus ground wire sizing per Table C1 from Appendix C.
Only 6 and 9 kW models can be field converted to single- or three-phase (open delta on 3-phase). Check wiring diagram supplied
with the unit when converting the phase of a unit. Larger branch circuit required than for balanced 3-phase of equal kW. Balanced
3-phase available, consult factory.
NOTE: 250 kcmil maximum wire size for terminal block.
WARNING! Consult a licensed electrical contractor for proper electrical installation conforming to local electrical codes
and the National Electrical Code (N.E.C.).