7. If improper venting is observed during any of the above tests, 
the venting system must be corrected.
FAIlUre  TO  COrreCT  bACK  DrAFTS  MAY  CAUSe  AIr 
COnTAMInATIOn AnD UnSAFe COnDITIOnS.
•  If the back draft cannot be corrected by the normal method or 
if a suitable draft cannot be obtained, a blower type flue gas 
exhauster  must  be  employed  to  assure  proper  venting  and 
correct combustion.
CheCking the input
Follow these instructions to determine the firing rate of the water 
heater.
1. Follow the procedure described in the "Initial Start Up" section 
on  page  24  to  measure  the  static  and  dynamic  supply  gas 
pressures.  Verify  that  the  static  and  dynamic  supply  gas 
pressures conform to the values listed in Table 3 on page 8.
2. Use this formula to “clock” the meter.  be sure that other gas 
consuming appliances are not operating during this interval.
  (3600/T) x H = btuh
  T  =  Time in seconds to burn one cubic foot of gas.
  H = btu’s per cubic foot of gas.
  btuh = Actual heater input.
  example: (Using (A)bCl3 85T275 6nOX heater)
  T = 13.1 seconds
  H = 1000 bTU/Cu.Ft.
  btuh = (3,600/13.1) x 1,000 = 275,000
  (Compare with (A)bCl3 85T275 6nOX model and rating.)
UnDer nO CIrCUMSTAnCeS SHOUlD THe GAS InPUT eXCeeD 
THe  InPUT  SHOWn  On  THe  HeATer'S  rATInG  PlATe.
water temperature adjustment
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
The  water  temperature  is  controlled  by  a  thermostat,  Fig.  3, 
which has two sensing elements. One sensor is located near the 
top of the tank and the other is near the center. The thermostat 
is set in the lowest position before the heater leaves the factory.
The  thermostat  temperature  dial,  Fig.  3,  is  accessible  by 
removing the control cover. The dial is adjustable and may be set 
for 120°F (49°C) to 180°F (82°C) water temperature, but 120°F 
(49°C) is the recommended starting point. It is suggested the dial 
be placed on the lowest setting which produces an acceptable 
hot water supply. This will always give the most energy efficient 
operation. The temperature control has a 4°F fixed differential.
Supply gas pressure shall be measured while the water heater 
is not firing (static pressure) and while the water heater is firing 
at full capacity (dynamic pressure). 
If the supply gas pressure to the water heater is not between 
the  required  minimum  and  maximum  values  given  in  Table  3 
on page 8 adjust the supply gas regulator as necessary. Adjust 
the  supply  gas  regulator(s)  per  the  regulator  manufacturer’s 
instructions  to  achieve  the  required  “static”  and  “dynamic” 
supply gas pressure.
multiple appliance installations:
In  multiple  water  heater  installations  or  in  installations  where 
the installed water heater(s) share a common gas supply main 
with other gas fired appliances; the supply gas pressures shall 
be measured at each water heater with all gas fired appliances 
connected to a common main firing at full capacity.
On multiple water heater installations the supply gas line regulators 
shall be adjusted to provide gas pressure to each water heater 
within the minimum and maximum supply pressure requirements 
listed in Table 3 on page 8 with all gas fired appliances connected 
to a common gas main firing at full capacity.
note:  A  pressure  drop  of  more  than  1.5”  W.  C.  (0.37  kPa) 
when the Main burner ignites is an indication of an inadequate 
supply of gas and can lead to ignition failure, rough starts and/
or rough operation. If a drop of more than 1.5” W. C. (0.37 kPa) 
in  supply  gas  pressure  occurs  when  the  Main  burner  ignites, 
ensure the supply gas lines and regulator(s) are properly sized 
and installed. See the requirements for Supply Gas regulator 
on page 12 and Gas Piping on page 23. ensure all requirements 
and installation instructions are maintained.
CheCking Venting
The  following  steps  shall  be  followed  with  each  appliance 
connected to the venting system placed in operation, while any 
other  appliances  connected  to  the  venting  system  are  not  in 
operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as 
required in the national Fuel Gas Code, AnSI Z223.1or the CAn/
CGA b149 Installation Codes and these instructions. Determine 
that there is no blockage or restriction, leakage, corrosion and 
other deficiencies which could cause an unsafe condition.
3. So far as is practical, close all building doors and windows 
and all doors between the space in which the water heater(s) 
connected to the venting system are located and other spaces 
of the building. Turn on all appliances not connected to the 
venting system. Turn on all exhaust fans, such as range hoods 
and  bathroom  exhausts,  so  they  shall  operate  at  maximum 
speed. Close fireplace dampers.
4. Follow the lighting instruction.  Place the water heater being 
inspected in operation.  Adjust thermostat so appliance shall 
operate continuously.
5. Inspect vent system for leakage after 5 minutes of main burner 
operation.
6. After it has been determined that each appliance connected 
to the venting system properly vents when tested as outlined 
above,  return  doors,  windows,  exhaust  fans,  fireplace 
dampers and any other gas burning appliance to their previous 
conditions of use.