American Water Heater HPE10280H045DV Manuale Utente

Pagina di 48
10
tubing so that any discharge from the valve exits only within 
6 in. (152mm) above drain, or at any distance below, the 
structural fl oor, and does not contact any live electrical part. 
The discharge opening must not be blocked or reduced in 
size under any circumstance. 
IMPORTANT:  Only a new temperature and pressure relief 
valve should be used with your water heater. Do not use an 
old or existing valve as it may be damaged or not adequate 
for the working pressure of the new water heater. Do 
not place any valve between the relief valve and the 
tank.
The Temperature & Pressure Relief Valve:   
• 
Shall not be in contact with any electrical part.
• 
Shall be connected to an adequate discharge line.
• 
Shall not be rated higher than  the working pres-
sure   shown on the data plate of the water heater.
The Discharge Line:
• 
Shall not be smaller than the pipe size of the relief  
valve or have any reducing coupling installed in the 
discharge line.
• 
Shall not be capped, blocked, plugged or contain 
any valve between the relief valve and the end of 
the discharge line.
• 
Shall terminate a maximum of 6 in. (152mm) above 
a floor drain or external to the building. In cold 
climates, it is recommended that the discharge pipe 
be terminated at an adequate drain inside the build-
ing.
• 
Shall be of material listed for hot water distribution.
• 
Shall be installed to allow complete drainage of 
both the valve and discharge line.
Explosion Hazard
‡ 7HPSHUDWXUHSUHVVXUHUHOLHI
YDOYHPXVWFRPSO\ZLWK$16,
=&6$DQG$60(
FRGH
‡ 3URSHUO\VL]HGWHPSHUDWXUH
SUHVVXUHUHOLHIYDOYHPXVWEH
LQVWDOOHGLQRSHQLQJSURYLGHG
‡ &DQUHVXOWLQRYHUKHDWLQJ
DQGH[FHVVLYHWDQNSUHVVXUH
‡ &DQFDXVHVHULRXVLQMXU\RU
GHDWK
6” (152mm)
Maximum 
Air Gap
Drain Pan 
2 1/2” (63.5mm) 
Depth Maximum and
2” (51mm) wider than
the water heater.
Discharge Pipe
(Do Not Plug or Cap)
Temperature and 
Pressure Relief Valve
Drain Line 3/4” (19mm) 
ID Minimum
Drain
Figure 3
Temperature and Pressure 
Relief Valve Installation 
For protection against excessive pressures and 
temperatures, a temperature and pressure relief valve must 
be installed in the opening marked “T & P RELIEF VALVE” 
(Figure 3).
To reduce the risk of excessive pressures and temperatures 
in this water heater, install temperature and pressure relief 
protective equipment required by local codes, but no less 
than a combination temperature and pressure relief valve 
certifi ed by a nationally recognized testing laboratory that 
maintains periodic inspection of the production of listed 
equipment or materials, as meeting the requirements for 
Relief Valves and Automatic Shutoff Devices for Hot Water 
Supply Systems, ANSI Z21.22 - latest edition. This valve must 
be marked with the maximum set pressure not to exceed 
the marked maximum working pressure of the water heater. 
Install the valve into an opening provided and marked for 
this purpose in the water heater, and orient it or provide 
Temperature and Pressure Relief Valve
Closed System/Thermal Expansion
As water is heated, it expands (thermal expansion). In 
a closed system, the volume of water will grow. As the 
volume of water grows, there will be a corresponding 
increase in water pressure due to thermal expansion. 
Thermal expansion can cause premature tank failure 
(leakage). This type of failure is not covered under 
the limited warranty. Thermal expansion can also 
cause intermittent temperature-pressure relief valve 
operation: water discharge from the valve due to 
excessive pressure build up. The temperature pressure 
relief is not intended for the constant relief of thermal 
expansion. This condition is not covered under the 
limited warranty.
A properly-sized thermal expansion tank should be 
installed on all closed systems to control the harmful 
effects of thermal expansion. Contact a plumbing 
service agency or your retail supplier reguarding the 
installation of a thermal expansion tank.