American Water Heater (A)BCG3 85T500-8N Manuale Utente

Pagina di 52
15
through the water heater’s vent system causing poor combustion. 
Sooting, serious damage to the water heater and the risk of fire 
or explosion may result. It can also create a risk of asphyxiation.
louVers and grilles
The free areas of the fresh air openings in the instructions that 
follow do not take in to account the presence of louvers, grilles 
or screens in the openings.
The  required  size  of  openings  for  combustion,  ventilation 
and dilution air shall be based on the “net free area” of each 
opening. Where the free area through a design of louver or 
grille  or  screen  is  known,  it  shall  be  used  in  calculating  the 
size  of  opening  required  to  provide  the  free  area  specified. 
Where  the  louver  and  grille  design  and  free  area  are  not 
known, it shall be assumed that wood louvers will have 25% 
free  area  and  metal  louvers  and  grilles  will  have  75%  free 
area. Non motorized louvers and grilles shall be fixed in the 
open position.
Vent adapter
The (A)BCG385T500-8N/(A)BCG385T500-8P model is shipped 
with a 6" to 8" diameter vent adapter (Fig. 11). The vent adapter 
fits  on  top  of  the  installed  blower  exhaust.  Use  only  vent 
adapters supplied with the unit. The venting must comply with 
the NATIONAL FUeL GAS CODe, ANSI Z223.1/NFPA 54 and 
for Canadian installations consult the Canadian Installation Code 
CAN/CSA B149.1-00.
figure 11
Never obstruct the flow of ventilation air. If you have any doubts 
or questions at all, call your gas supplier. Failure to provide the 
proper amount of combustion air can result in a fire or explosion 
and cause property damage, serious bodily injury or death.
unconfined space
An Unconfined Space is one whose volume IS NOT LeSS ThAN 
50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the 
total input rating of all appliances installed in the space. rooms 
communicating directly with the space, in which the appliances 
are  installed,  through  openings  not  furnished  with  doors,  are 
considered a part of the unconfined space.
Makeup  air  requirements  for  the  operation  of  exhaust  fans, 
kitchen ventilation systems, clothes dryers and fireplaces shall 
also be considered in determining the adequacy of a space to 
provide combustion, ventilation and dilution air.
unusually tight construction
In unconfined spaces in buildings, infiltration may be adequate 
to  provide  air  for  combustion,  ventilation  and  dilution  of  flue 
gases. however, in buildings of unusually tight construction (for 
example,  weather  stripping,  heavily  insulated,  caulked,  vapor 
barrier, etc.) additional air must be provided using the methods 
described in the Confined Space section that follows.
confined space
A Confined Space is one whose volume IS LeSS ThAN 50 cubic 
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 
rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, 
ventilation and dilution in confined spaces. The required size for 
the openings is dependent on the method used to provide fresh 
air to the confined space AND the total Btu/hr input rating of all 
appliances installed in the space.
exhaust fans
Where exhaust fans are installed, additional air shall be provided 
to replace the exhausted air. When an exhaust fan is installed 
in  the  same  space  with  a  water  heater,  sufficient  openings  to 
provide  fresh  air  must  be  provided  that  accommodate  the 
requirements for all appliances in the room and the exhaust fan. 
Undersized openings will cause air to be drawn into the room 
Venting installation
Venting
The INSTrUCTIONS IN ThIS SeCTION ON VeNTING MUST 
Be  FOLLOWeD  TO AVOID  ChOkeD  COMBUSTION  Or 
reCIrCULATION  OF  FLUe  GASeS.    SUCh  CONDITIONS 
CAUSe SOOTING Or rISkS OF FIre AND ASPhyXIATION.
heater must be protected from freezing downdrafts.
remove all soot or other obstructions from the chimney that will 
retard a free draft.
Type  B  venting  is  recommended  with  these  heaters.  For 
typical venting application see TeChNICAL DATA VeNTING 
on page 18. 
This  water  heater  must  be  vented  in  compliance  with  all  local 
codes,  the  current  revision  of  the  National  Fuel  Gas  Code 
(ANSI-Z223.1) and with the Category I Venting Tables.
If any part of the vent system is exposed to ambient temperatures 
below 40°F it must be insulated to prevent condensation.
•  Do not connect the heater to a common vent or chimney 
with  solid  fuel  burning  equipment.    This  practice  is 
prohibited  by  many  local    building  codes  as  is  the 
practice of venting gas fired equipment to the duct work 
of ventilation systems.
      
 figure 12
•  Where a separate vent connection is not available and the 
vent pipe from the heater must be connected to a common