Specifications
Power requirements 96D
17-27 Vac, 50/60 Hz, 8.64 VA
18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)
Operating temperature range
-20°C to 50°C (-4°F to 122°F)
Operating humidity range
0 to 95% RH (non-condensing)
Operating altitude
Up to 3000 m (9843 ft)
Network capacity
Up to 96 transmitters, 32 per channel
Channels 1, 2 = Modbus
Channel 3 = Modbus only
Communication 
Up to 609m (2,000 ft) per channel
(length of lines)
T-tap maximum = 20m (65 ft) per t-tap, 
overall total of 40m (130 feet)
User interface
Graphic 122 x 32 dot matrix backlit display
User friendly keypad
Visual indicators
Power      Green LED
Warn, Alarm, High Alarm   Red LED
Fault          Amber LED
Tx              Amber LED
Rx             Green LED
Outputs
4 DPDT relays
Output rating
5A, 30Vdc or 250 Vac (resistive load)
Audible alarm
65dBA at 1 m (3 ft)
Time delays
Programmable Before and After delays
Battery
3 volt lithium battery
Enclosure Painted 
aluminum 
Dimensions (HxWxD)
9.5” x 14” x 3.5” (24.1 x 35.6 x 8.9 cm)
Certifications
ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662