(2)  Run/stop command terminal (FWD, REV) 
  FWD terminal is short-circuit to CM terminal in the factory.  Pressing the RUN key on the keypad 
panel can start forward operation.  If function F02 is 0, short-circuit FWD and CM and press the 
RUN key for forward operation, or short-circuit REV and CM for reverse operation.  If function F02 is 
1, then short-circuit FWD and CM for forward operation, or REV and CM for reverse operation.  
Regardless of whether function F02 is set to 0 or 1, short-circuiting both FWD – CM and REV – CM 
brings the drive to a deceleration-stop. Refer to F02 “Operation method” for details. 
 
(3)  Analog input terminal (13, 12, 11, C1) 
  Use these terminals to connect external input analog voltage and analog current and frequency 
setting device (POT).  For connecting a contact to this circuit, use a twin contact for fine current sig-
nal.   Do not use a contact for terminal 11. 
 
 
 
 
 
 
!
WARNING 
 
1.  The STOP key is valid only when the function has been set.  Prepare an-
other switch for emergency stop.  When the data of F02 is selecte “2” or “4”, 
the operation cannot be stopped using the STOP key on the keypad panel, 
otherwise accidents could occur.
 
 
*Note the following when wiring: 
(1) Surge absorber connection 
When the exciting coil of the magnetic contactor or relay in 
the control circuit or drive peripheral circuit is opened or 
closed, a surge voltage (noise) is generated with a sudden 
current change.  Due to this surge voltage, the drive control 
circuit or peripheral equipment may malfunction.  If so, directly 
connect a surge absorber to both ends of the coil.  (See Fig-
ure 2-3-4).) 
 
(2) Control circuit wiring 
1  Wires connected to control circuit terminals must be AWG 
20 (0.5mm
2
) shielded wire or twisted vinyl wire. Remove 
the sheath as shown in Figure 2-3-5 and then connect it. 
2  Keep the wiring of the main circuit, external relay se-
quence circuit and control circuit as far away from each 
other as possible. If they must be adjacent, cross 
them at right angles. 
3  Use a twisted-pair shielded wire for long wiring 
distances. 
 
(3) Shielding sheath connection 
Connect one end of the shielding sheath of a shielded 
or twisted-pair shielded wire to the ground terminal as 
shown in Figure 2-3-6. Do not connect the other end. 
 
 
 
 
 
 
 
 
 
 
 
 
 
SK: Surge absorber     D: Diode 
 
Figure 2-3-4  Surge absorber  
             connection diagram 
 
 
 
 
Figure 2-3-5  End treatment 
 
 
 
 
 
 
 
 
 
 
Figure 2.3.6 Connection of sheath  
            of shielded wire
 
+
 
-
 
Ry
 
D
 
MC
 
SK
 
AC relay 
DC relay 
 0.24” 
± 0.04”  (6±1mm) 
To ground terminal
 
To ground terminal
 
CM
 
13
 
12
 
11
 
Contact 
Shielded wire 
FWD
 
Frequency  
setting POT
 
Shielded wire