Step 1:  With the handle inserted into the actuating 
shaft, move handle UP. Be sure to hold on to 
the handle as it will move quickly after the 
center of travel.
3.2.2   CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch 
by observing the position of the manual operation 
handle in Figure 3.1. If the handle is DOWN, the 
contacts are closed in the EMERGENCY (STANDBY) 
position. No further action is required. If the handle 
is UP, proceed with Step 1.
Step 1:  With the handle inserted into the actuating 
shaft, move the handle DOWN. Be sure to 
hold on to the handle as it will move quickly 
after the center of travel.
3.2.3   RETURN TO NORMAL SOURCE SIDE
Manually actuate switch to return manual operating 
handle to the UP position.
‹
‹
3.3 VOLTAGE 
CHECKS
1.  Turn ON the UTILITY power supply to the trans-
fer switch with whatever means provided (such as 
the UTILITY main line circuit breaker).
DANGER
  PROCEED WITH CAUTION. THE TRANSFER 
SWITCH IS NOW ELECTRICALLY HOT. CONTACT 
WITH LIVE TERMINALS RESULTS IN EXTREMELY 
HAZARDOUS AND POSSIBLY FATAL ELECTRICAL 
SHOCK.
2.  
With an accurate AC voltmeter, check for correct 
voltage.
 
Single-phase utility supply:
 
Measure across ATS terminal lugs N1 and N2. Also 
check N1 to NEUTRAL and N2 to NEUTRAL.
3.  When certain that UTILITY supply voltage is cor-
rect and compatible with transfer switch ratings, 
turn OFF the UTILITY supply to the transfer 
switch.
4.  
On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL position. The gen-
erator should crank and start.
Section 3 — Operation
“HS” Type Transfer Switch
Attach handle to actuating shaft.
Move handle
UP for the
NORMAL
(UTILITY)
position.
Move handle
DOWN for the
EMERGENCY
(STANDBY)
position.
NOTE:  Return handle to
storage position in enclosure
when finished with manual transfer.
Figure 3.1 — Actuating Transfer Switch