SECTION 9: GAS PIPING
Install the gas hose as shown in 
Figure 21. The gas 
hose accommodates expansion of the heating 
system and allows for easy installation and service of 
the burner. Before connecting the burners to the 
supply system, verify that all high pressure testing of 
the gas piping has been completed.
There is an expansion of the tube with each firing 
cycle. This will cause the burner to move with respect 
to the gas line. This can cause a gas leak resulting in 
an unsafe condition if the gas connection is not made  
in strict accordance with 
Meter and service must be large enough to handle all 
the burners being installed plus any other connected 
load. The gas line which feeds the system must be 
large enough to supply the required gas with a 
maximum pressure drop of 1/2" wc When gas piping 
is not included in the layout drawing, the local gas 
supplier will usually help in planning the gas piping.
Gas lines must meet applicable codes: 
United States: The Flexible Stainless Steel Gas 
Hose (US models) supplied with the heater is 
certified per the Standard for Connectors for Gas 
Appliances, ANSI Z21.24/CSA 6.10 - latest revision. 
Canada: The Rubber Type 1 Gas Hose (Canadian 
models) optional with the heater is certified as being 
in compliance with the Standard for Elastomeric 
Composite Hose and Hose Couplings for Conducting 
Propane and Natural Gas, CAN/CGA 8.1 - Latest 
revision.
• Check the pipe and tubing ends for leaks 
before placing heating equipment into ser-
vice. When checking for gas leaks, use a soap 
and water solution; never use an open flame.
WARNING
Fire Hazard
Tighten gas hose fittings to connect gas 
supply according to Figure 21.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Use only 36" (91 cm) long connector of 1/2" or 
3/4" nominal ID.
Connector supplied with heater for U.S. 
models (not with Canadian models).
Failure to follow these instructions can result 
in death, injury or property damage.
WARNING
Explosion Hazard
Leak test all components of gas piping 
before operation.
Gas can leak if piping is not installed 
properly.
Do not high pressure test gas piping with 
heater connected.
Failure to follow these instructions can result 
in death, injury or property damage.