Delta Tau 3Ax-602646-xUxx Manuale Utente

Pagina di 40
 
 
Quad Amp Hardware Reference Manual 
 
Introduction 
6
Protection 
There are several layers of protection built into the amplifier, including transient voltage filters, transient 
surge suppressors, fuses, a flyback diode, and a variety of fault detection circuits.  These are discussed in 
the following paragraphs and in the Troubleshooting Chapter. 
Transient Voltage Filter  
The transient voltage RC filter is used as a means of suppressing inductive transients and is located across 
the single phase Control AC input voltage connector C3. 
Transient Surge Suppressors  
Transient surge suppressors (also referred to as metal oxide varistors or MOVs) are connected across all 
three input phases (L1, L2, L3) of the Main AC input power.  They are located on a circuit board attached 
to the top of the bridge power rectifier.  The primary function of these devices is to absorb high-level 
energy pulses (spikes). 
Fly-Back Diode 
The fly-back diode clamps inductive spikes that may be generated across the external shunt resistors 
when the shunt IGBT is turned off.  The diode is connected across the external shunt resistor terminals. 
Fuses 
The primary hardware protection is fuses, which are mounted within the Quad Amplifier chassis. 
Fuse F201 
F201 is a 30 Amp long delay fuse, located externally on the top cover of the Quad Amplifier.  Fuse F201 
is connected to the output of the shunt regulator IGBT and to the internal shunt regulator resistors.  Fuse 
F201 protects the shunt regulator IGBT and the internal shunt resistors from over current damage. 
Fuse F202 
F202 is a 4-Amp Slo-Blo fuse located under the Quad Amplifier cover, next to the control AC input 
power supply transformer.  This fuse is connected between incoming AC control input power connector 
C3 and control input AC power transformer T201.  Fuse F202 protects the primary input windings of the 
control power supply transformer against overloads. 
Ground Fault (GF) 
The Ground Fault Detector is a self-powered circuit that continuously samples the AC line currents via a 
toroid around the incoming three phase lines.  If there is more current flowing into the amplifier than out, 
the ground fault circuit will activate and shut down the Quad Amplifier with a soft start fault.