EPN-SNTY (EPN Sanity Audit) 
9
Error Log Entries and Test to Clear Values
Notes:
a. Error 8801 occurs whenever the EPN is unable to send up-link control 
messages and the control channel of the TDM Bus in the EPN has been 
switched as part of the recovery procedure.
b. Error 8803 occurs each time whenever the EPN is unable to send up-link 
control messages and the EPN Tone-Clock has been switched as part of 
the recovery procedure.
c. Error 9901 occurs whenever the EPN is unable to send up-link control 
messages, but recovers after the control channels of the TDM Bus in the 
EPN are switched.
d. Error 9902 occurs whenever the EPN is unable to send up-link control 
messages, but recovers after the active Tone-Clock in the EPN is 
switched.
e. Error 9903 occurs whenever the EPN is unable to send up-link control 
messages, but recovers after a PNC interchange has taken place.
f. Error 9904 occurs whenever the EPN is unable to send up-link control 
messages, but recovers after an EPN WARM reset.
g. Error 9905 occurs whenever the EPN is unable to send up-link control 
messages, but recovers after an EPN COLD reset.
Table 9-294.
EPN-SNTY Error Log Entries
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
1
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0
Any
None
8801 (a)
Any
None
8803 (b)
Any
None
9901 (c)
Any
None
9902 (d)
Any
None
9903 (e)
Any
None
9904 (f)
Any
None
9905 (g)
Any
None