Lucent Technologies Release 7 Manuale Utente
DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-10
AC-POWER
9
AC Power Query Test (#78)
This test is not valid for DC-powered cabinets and should always abort or pass.
Table 9-4. TEST #78 Power Query Test
Error
Code
Code
Test
Result
Description/Recommendation
1000
ABORT
System resources required to run test are not available.
100
2000
2000
ABORT
Response to the test request was not received within the allowable time
period.
period.
2029
2319
2320
2500
2319
2320
2500
ABORT
Internal system error.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
Any
FAIL
The SYSAM in a PPN or the EPN Maintenance circuit pack in an EPN is
incorrectly reporting an AC power problem. If this test fails, there is a
problem with the SYSAM OR EPN Maintenance circuit pack. Replace the
suspect circuit pack and run the test again. (b)
incorrectly reporting an AC power problem. If this test fails, there is a
problem with the SYSAM OR EPN Maintenance circuit pack. Replace the
suspect circuit pack and run the test again. (b)
PASS
Since this test is invalid for DC-powered cabinets, this result simply
indicates that the SYSAM or EPN Maintenance circuit pack is handling this
test properly
indicates that the SYSAM or EPN Maintenance circuit pack is handling this
test properly
Continued on next page