Install and Connect Cabinets
Page 1-18
Connect DC Power and Ground
1
DC Power and Ground (J58890CF Only)
Figure 1-7
shows a typical power and ground layout for a DC-powered cabinet.
The size of the wire required for the -48 volt DC and -48 volt return must ensure
the -48 volt DC supplied by the battery plant is maintained between -42.5 and
-54.2 volts DC at all times for proper operation and to prevent hardware damage.
This procedure applies to both PPN and EPN cabinets.
the -48 volt DC supplied by the battery plant is maintained between -42.5 and
-54.2 volts DC at all times for proper operation and to prevent hardware damage.
This procedure applies to both PPN and EPN cabinets.
Figure 1-7.
Typical Power and Ground for a DC-Powered Cabinet