OUTLET MANAGED PDU
 
44
  On - Callback ONLY (With Password Prompt):  Callbacks will be 
performed for accounts that include a Callback Number, and the username/
password prompt will be displayed when the user’s modem answers (users 
will be required to re-enter their username/password when their modem 
answers.)  Accounts that do not include a Callback Number will not be able 
to access command mode via modem.
•  Callback Attempts:  The number of times that the Outlet Managed PDU will 
attempt to contact the Callback number.  (Default = 3 attempts.)
•  Callback Delay:  The amount of time that the Outlet Managed PDU will wait 
between Callback attempts.  (Default = 30 seconds.)
Notes:
•  After configuring and enabling Callback Security, you must then 
define a callback phone number for each desired user account 
(as described in Section 5.5) in order for this feature to function 
properly.
•  When using the "On - Callback (With Password Prompt)" option, 
it is important to remember that accounts that do not include 
a callback number will be allowed to access command mode 
without callback verification.
5.3.5.  Power Source Configuration
The Power Configuration menu allows you to adjust power measurements in order 
to obtain a more accurate determination of how much "real power" is being used by 
devices connected to the Outlet Managed PDU.  Real Power is determined by the 
following equation:
Real Power = 
(Voltage * Amps) * Power Factor
Power Efficiency
To define Power Configuration parameters, access the command mode using an 
account that permits access to Administrator level commands and then activate the 
System Parameters Menu.
Notes:
•  In the Text Interface, power source configuration parameters are 
defined via the Power Configuration menu.
•  In the Web Browser Interface, power source configuration 
parameters are selected via the System Parameters menu.