36 
14.7 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches are color coded for each pressure setting.
Carry out a commission after working on or changing a pressure switch. See Page 19, Section 10.
14.8 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their 
positions.
Release the four mounting standoffs.
Refit in reverse. Ensure correct location of ignition cable and all other wiring.
14.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch or disabling
pressure switch circuit could cause unsafe condition.
Failure to follow these instructions can result in
death or serious injury.
WARNING
MODEL
UHA[S]
150 - 175
UHA[S]
200 - 225
UHA[S]
250
UHA[S]
300 - 350
UHA[S]
400
Pressure Switch 
Kit P/N
90439802
90439808
90439803
90439807
90439808
Color Code
yellow
orange
gray
brown
orange
Set Point in. w.c.
.32
.79
.41
.68
.79
Pressure Switch Snap 
Ring P/N
90439850
90439850
90439850
90439850
90439850
MODEL
UHA[S] 150 - 175
 UHA[S] 200- 250
 UHA[S] 300 - 400
Axial Fan Guard
91901105
91901104
91901105
Axial Fan Motor
90600106
90600107 
90600106 
Axial Fan Blade
90709005
90709006 
90709005