SECTION 3: C
RITICAL
 C
ONSIDERATIONS
3
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[S] heaters have automatic ignition burners for 
ON/OFF operation only. 
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with 
horizontal discharge.
• May be mounted on a shelf of non-combustible 
material.
• May be suspended from above (See Page 6, 
Figure 2
) or from wall brackets of sufficient 
strength to support the heater as listed in the 
Dimension Data Table on Page 38, Section 15.1
Drop rods must be a minimum of 3/8" diameter 
mild steel. Four suspension points (3/8" nuts) 
are located on top of the heater. 
• Must be installed in a manner which allows 
access to all serviceable components.
See Page 4, Figure 1
 for details.
3.3 Minimum Required Installation Clearances
Clearances around the heater and vent must be as 
indicated on Page 4, Figure 1Page 9, Figure 3 
through Page 12, Figure 8
 to ensure access for 
servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure 
1
. If clearances to combustibles are not indicated, 
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air 
space around the heater to supply air for 
combustion, ventilation and distribution in 
accordance with local and national codes on Page 7, 
Section 6
3.6 Gas Supply
It is important that the gas supply pipe is sized 
correctly to provide the inlet pressure as stated on 
the heater data plate. The gas supply pipe and 
electrical connections must not support any of the 
heater's weight on Page 14, Section 8
3.7 Electrical Supply
A permanent 120 V 60 Hz 1 Ø electrical supply is 
required for the main electrical power. The heater 
also requires suitable controls in accordance with 
See Page 15, Section 9
.
3.8 Vent 
Choose heater orientation to allow for the proper 
location of the vent. Each heater must be fitted with 
a correctly sized sealed vent system. 
If vented horizontally, no other appliance may be 
connected to the vent. See Page 7, Section 6.
3.9 Separated Combustion Installation
For separated combustion installation, the vent and 
air intake must be fitted with an individual and 
correctly sized sealed system and the vent and air 
intake must terminate at approved wall and roof 
terminals.
Separated combustion units may not be common 
vented. See Page 7, Section 6.