SECTION 5: H
EATER
 I
NSTALLATION
7
SECTION 5: HEATER INSTALLATION
5.1 General 
Heaters are designed for installation above 1.8 m. 
These heaters must be installed within the heated 
space. Duct delivery systems are not permitted with 
axial fans. When handling or supporting the heater 
from below, ensure that the weight is taken at the 
support points.
5.2 Shelf Mounting and Suspension
For typical suspension, See Page 7, Figure 2.
5.3 Wall Mounting
For typical suspension, See Page 8, Figure 3
Heaters blowing parallel to the wall can only be 
installed with the service door away from the wall.
The wall mounting brackets must be attached to a 
suitable wall through all mounting holes. Screw 
sizes less than M10 may not be used. In order for 
the wall mounting brackets to adequately carry the 
weight of the heater, it must be installed with best 
building practice.
Figure 2: Suspension Methods
Existing cabinet screws must be re-used.
WARNING
Crush Hazard
Use 10 mm steel drop rod
minimum.
Failure of the supports can
result in death, injury
or property damage.
Cone Point
Set Pin
Window
Clamp
Unistrut
10 mm
Steel
Drop Rod
Nut
Washer
Riv
Nut
Support Points
Ensure all suspension hardware
is torqued to a minimum
of  27 Nm (20 ft lbs).
NOTE: For vertical installations, use the mounting points on the rear of the unit.
10 mm
Steel
Drop Rod
Washer
Nut
Unistrut
Channel Nut
Shelf Mounting
Brackets
Description
Part Number
Qty.
Shelf Mounting Bracket 
Kit
11111510K
  Shelf Mounting Bracket (2)
111111510
2
  Screw #10 x 1/2" 
  Type AB Phil HWH Z (2)
94311008
2