Part 2
operation (8/10 kW)
STARTUP:
When the engine is started, residual magnetism from 
the  rotor  induces  a  voltage  into  (a)  the  stator  AC 
power windings, and (b) the stator excitation or DPE 
windings. The  capacitor  on  the  DPE  winding  will  be 
charged and then will discharge causing a voltage to 
be induced back into the rotor. 
FIELD EXCITATION:
An  AC  voltage  is  induced  into  the  stator  excitation 
(DPE) windings. The DPE winding circuit is completed 
to the capacitor, via Wire 2 and Wire 6.
The  capacitor  will  charge  at  a  rate  that  is  dependant 
on the amount of voltage that is being induced into it. 
Once  the  capacitor  is  fully  charged  the  voltage  that 
it  discharges  is  a  constant  voltage  and  will  in-turn 
increase the size of the magnetic field of the rotor.
The greater the current flow through the rotor windings, 
the more concentrated the lines of flux around the rotor 
become.
The  more  concentrated  the  lines  of  flux  around  the 
rotor  that  cut  across  the  stationary  stator  windings, 
the  greater  the  voltage  that  is  induced  into  the  stator 
windings.
AC POWER WINDING OUTPUT:
A  regulated  voltage  is  induced  into  the  stator  AC 
power windings. When electrical loads are connected 
across the AC power windings to complete the circuit, 
current can flow in the circuit. 
operation (12-20 kW)
STARTUP:
When the engine is started, residual plus field boost 
magnetism  from  the  rotor  induces  a  voltage  into 
(a)  the  stator  AC  power  windings,  and  (b)  the  sta-
tor  excitation  or  DPE  windings.  In  an  “on-speed” 
condition,  residual  plus  field  boost  magnetism  are 
capable of creating approximately one-half the unit’s 
rated voltage.
ON-SPEED OPERATION:
As the engine accelerates, the voltage that is induced 
into  the  stator  windings  increases  rapidly,  due  to  the 
increasing speed at which the rotor operates.
FIELD EXCITATION:
An  AC  voltage  is  induced  into  the  stator  excitation 
(DPE)  windings.  The  DPE  winding  circuit  is  complet-
ed  to  the  voltage  regulator,  via  Wire  2  and  Wire  6. 
Unregulated alternating current can flow from the wind-
ing to the regulator.
The voltage regulator “senses” AC power winding out-
put voltage and frequency via stator Wires 11 and 22.
The  regulator  changes  the  AC  from  the  excitation 
winding  to  DC.  In  addition,  based  on  the  Wires  11 
and 22 sensing signals, it regulates the flow of direct 
current to the rotor.
The rectified and regulated current flow from the regu-
lator is delivered to the rotor windings, via Wire 4, and 
the positive brush and slip ring. This excitation current 
flows  through  the  rotor  windings  and  is  directed  to 
ground  through  the  negative  (-)  slip  ring  and  brush, 
and Wire 0.
The greater the current flow through the rotor windings, 
the more concentrated the lines of flux around the rotor 
become.
The  more  concentrated  the  lines  of  flux  around  the 
rotor  that  cut  across  the  stationary  stator  windings, 
the  greater  the  voltage  that  is  induced  into  the  stator 
windings.
Initially, the AC power winding voltage sensed by the 
regulator  is  low.  The  regulator  reacts  by  increasing 
the  flow  of  excitation  current  to  the  rotor  until  volt-
age  increases  to  a  desired  level. The  regulator  then 
maintains the desired voltage. For example, if voltage 
exceeds the desired level, the regulator will decrease 
the  flow  of  excitation  current.  Conversely,  if  voltage 
drops below the desired level, the regulator responds 
by increasing the flow of excitation current.
AC POWER WINDING OUTPUT:
A  regulated  voltage  is  induced  into  the  stator  AC 
power windings. When electrical loads are connected 
across  the  AC  power  windings  to  complete  the  cir-
cuit,  current  can  flow  in  the  circuit.  The  regulated 
AC  power  winding  output  voltage  will  be  in  direct 
proportion to the AC frequency. For example, on units 
rated  120/240  volts  at  60  Hz,  the  regulator  will  try  to 
maintain 240 volts (line-to-line) at 60 Hz. This type of 
regulation  system  provides  greatly  improved  motor 
starting capability over other types of systems.
Page 36
AC GENERATORS
sEctioN 2.2
oPEratioNal aNalYsis