COLD WEATHER KIT
For cold climates, optional cold weather kit (part num-
ber 0F6148A) is recommended. The kit includes:
• Battery Warmer
•  4” Junction Box with Hardware
•  700 Cold Cranking Amp Battery
•  Thermostat; 20 deg “ON”, 40 deg “OFF”
•  6 qt. pack 5W-30 Synthetic Oil (engine)
•  1 qt. 75W90 Synthetic Gear Oil (gear drive)
‹
Figure 1 — Interconnections
6-2
Standby Generator Sets
Specifications
TO
ALTERNATOR
NEUTRAL
GROUND
CIRCUIT
BREAKER
NEUTRAL
Ground Level
Concrete Slab
STUB-UP AREA
See Install Dwg for
Dimensions
GENERATOR
CONNECTION
BOX
FRAME RAIL
H100   CONTROL
PANEL
Xfer
TO GENERATOR
CONNECTION BOX
Utility In
Load
Out
en
Battery
Transfer Switch
CIRCUIT BREAKER WIRE AND CONDUIT SIZE
KW     VOLTS        CB AMPS     LUG SIZE                 
130       240 1
        600        2-3/0 to 500 mcm       
130       208 3
        500        2-3/0 to 500 mcm                   
130       480 3 Ø        225         #6 to 350 mcm                   
2 WIRE
SHIELDED
CABLE
W/GROUND
TO
GENERATOR
CONNECTION
BOX
2 WIRE SHIELDED
CABLE W/GROUND
TO TRANSFER SW
GROUND AT GEN
CONNECTION BOX
ONLY
15 AMP 120
VOLT BATT
CHARGER
CIRCUIT
GenSpec010  Rev.
 C  11/05