TABLE C-2:  R7184 TROUBLESHOOTING 
Condition: Burner motor does not start when there is a call for heat. 
Procedure Status 
Corrective 
Action 
1.  Check that limit switches are 
closed and contacts are 
clean. This includes the 
burner motor reset button. 
N/A N/A 
2.  Check for line voltage power 
at the oil primary control. 
Voltage should be 120 Vac 
between the black and white 
lead wires on the oil primary 
control. 
N/A N/A 
Indicator light is on. 
Cad cell is defective, sees external light, or connections 
have shorted. Go to step 4. 
3.  Check indicator light with 
burner off, no call for heat (no 
flame). 
Indicator light is off. 
Go to step 5. 
Indicator light turns off. 
Eliminate external light source or permanently shield cad 
cell. 
4.  Shield cad cell from external 
light. 
Indicator light stays on. 
• 
Replace cad cell with new cad cell and recheck. 
• 
If indicator light does not turn off, remove yellow 
leadwires from R7184 and recheck. 
• 
If indicator light is still on, replace the R7184 
control. 
• 
If the indicator light turns off, replace cad cell 
bracket assembly. 
Burner starts. 
Trouble is in thermostat circuit. Check thermostat wiring 
connections. 
If connections are clean and tight, check thermostat wires 
for continuity. 
• 
Disconnect line voltage power and open line 
switch. 
• 
Check all wiring connections. 
• 
Tighten any loose connections and recheck. 
• 
If burner still doesn't start, replace R7184 
5.  Jumper thermostat (T -T) 
terminals on R7184 
 
 
IMPORTANT 
First remove one thermostat lead 
wire. 
Burner does not start. 
If burner still doesn't start, check the oil burner motor. It 
may be seized or burned out. 
 
Condition:  Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (½ second on, ½ second off) 
Procedure Status 
Corrective 
Action 
1.  Check that the limit switches 
are closed and contacts are 
clean. 
- - - 
- - - 
2.  Check for line voltage power 
at the oil primary control. 
Voltage should be 120 vac 
(nominal) 
- - - 
- - - 
Indicator light is on. 
Cad cell or controller is defective, sees external light, or 
connections are shorted. Go to step 4. 
3.  Check indicator light with 
burner off, no call for heat (no 
flame). 
Indicator light is off. 
Go to step 5. 
Continues on next page