RESET SETUP SUBMENU:
Press  
d
33) Display flashes 1
st
digit of the previous I
REST Reset value.
Press  
b & c 34) Press b and c buttons to enter a new “Reset” value.
Press  
d
35) Display shows 
STRD stored message momentarily and then
advances to 
RATE only, if it was changed, otherwise press a to
advance to 
RATE Rate Setup Submenu.
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
Press  
d
36) Display flashes 1
st
digit of previous D
RATE Rate value.
Press  
b & c 37) Press b and c buttons to enter a new RATE value.
Press  
d
38) Display shows 
STRD stored message momentarily and then
advances to the 
CYCL only, if it was changed, otherwise press a
to advance to 
CYCL Cycle Time submenu for RTD and
Thermocouple types. 
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
CYCLE TIME SUBMENU:
Press  
d
39) Display flashes 1
st
digit of the previous 
CYCL Cycle Time
value.
Press  
b & c 40) Press b and c buttons to enter a new “Cycle Time” value.
(1 to 199 seconds)
Press  
d
41) Display shows 
STRD stored message momentarily and then
advances to 
DPNG only, if it was changed, otherwise press a to
advance to 
DPNG Damping Factor Submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle. For example, a 15 second cycle time means that
every 15 seconds the output will turn on for part or all of the cycle. For Relay
control outputs, do not select a cycle time of less than 7 seconds or the relays’
lifetime will be shortened. For a cycle time of less than 7 seconds select SSR or
DC pulse. Use an external SSR with the DC pulse option for higher currents
(higher than 1 Amp).