Omega CNI16D Manuale Utente

Pagina di 72
56
ALARM 2 DISPLAY COLOR SUBMENU:
Press  
d
11) Display flashes previous selection for “Alarm 2 Color Display”.
Press  
b
12) Scroll through the available selections: 
GRN, RED or AMBR.
Press  
d
13) Display shows 
STRD stored message momentarily and then
momentarily shows the software version number, followed by
RST Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time when both Alarm 1
and  Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Output 1 & Output 2 = SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1
HI Value “ALR.H” = 400
"Color Display" Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN
RED
AMBER
•--➤------------------------------•-----------------------------•------------------------------➤
0                                  AL2.H = 200                AL1.H = 400        
Example 2:
Output 1 & Output 2 = Pulse
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1
Low Value  “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER
RED
GREEN
• --------------•----------------------------------•------------------------------------------- --•
0             AL1.L = 100                      AL2.L = 300