Forward Run/Stop and Reverse Run/Stop Commands: 
When you input the Run command via the terminal [FW], the inverter executes the Forward 
Run command (high) or Stop command (low). When you input the Run command via the 
terminal [RV], the inverter executes the Reverse Run command (high) or Stop command 
(low). 
 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
Inverter is in Run Mode, motor runs forward 
00 
FW Forward 
Run/Stop 
OFF
Inverter is in Stop Mode, motor stops 
ON 
Inverter is in Run Mode, motor runs reverse 
01 
RV Reverse 
Run/Stop 
OFF
Inverter is in Stop Mode, motor stops 
Valid for inputs: 
C001
~
C007
 
Required settings 
A002
 = 
01
 
Notes: 
•  When the Forward Run and Reverse Run 
commands are active at the same time, the 
inverter enters the Stop Mode. 
•  When a terminal associated with either [FW] or 
[RV] function is configured for normally closed
the motor starts rotation when that terminal is 
disconnected or otherwise has no input voltage. 
Example (default input configuration shown see 
page 66
): 
 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22
 
 
NOTE: The parameter 
F004
, Keypad Run Key Routing, determines whether the single Run 
key issues a Run FWD command or Run REV command. However, it has no effect on the 
[FW] and [RV] input terminal operation. 
 
WARNING: If the power is turned ON and the Run command is already active, the motor 
starts rotation and is dangerous! Before turning power ON, confirm that the Run command 
is not active. 
 
RV FW
 
7
6
5
4
3
2
1
 
L
 
P24
 
PLC