4.4.32. 
Map Descriptor Example 29 - read auxs 
//    Client Side Map Descriptors 
 
 
 
 
 
 
 
 
Map Descriptor 
 
 
 
 
 
 
 
Map_Descriptor_Name, 
Scan_Interval, 
Data_Array_Name, 
Data_Array_Offset, 
Function,  
Node_Name, 
SysPlus_Data_Type, 
Length 
All_Aux_States, 
0s, 
All_Aux_States, 
0, 
rdbc, 
SYSPLUS_01, 
All_Auxs, 
10 
 
The retrieved aux states will be stored as follows in Data_Array_Name: (A value of 1 will be stored for “on” or 0 for “off”) 
Offset from Data_Array_Offset  Description 
Aux_0 state 
Aux_1 state 
Aux_2 state 
.. 
.. 
Aux_9 state 
 
4.4.33. 
Map Descriptor Example 30 - read alarm status alarm 
//    Client Side Map Descriptors 
 
 
 
 
 
 
 
 
 
Map Descriptor 
 
 
 
 
 
 
 
 
Map_Descriptor_Name, 
Scan_Interval, 
Data_Array_Name, 
Data_Array_Offset, 
Function,  
Node_Name, 
SysPlus_Data_Type, 
SysPlus_Alarm_Name, 
Length 
Alarm_Sts_00, 
0s, 
Alarm_Statuses, 
0, 
rdbc, 
SYSPLUS_01, 
Alarm, 
volt, 
 
alarm is specified by the name under SysPlus_Alarm_Name.  The status of the alarm will be stored as 1 for “OK” or 0 for “FAIL” in 
Data_Array_Name at Data_Array_Offset. 
 
4.4.34. 
Map Descriptor Example 31 - emergency stop 
//    Client Side Map Descriptors 
 
 
 
 
 
 
 
Map Descriptors 
 
 
 
 
 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function,  
Node_Name, 
SysPlus_Cmd, 
Length 
Emergency_Stop, 
ProgSysControl, 
0, 
wrbx, 
SYSPLUS_01, 
Emergency_Stop, 
 
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.