4.4.86. 
Map Descriptor Example 82 - edit set events = event_list 
//    Client Side Mao Descriptors 
 
 
 
 
 
 
 
 
 
Map Descriptor 
 
 
 
 
 
 
 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function,   Node_Name, 
SysPlus_Cmd, 
Par_Data_Array_Name, 
Par_Data_Array_Offset, 
Length 
Ed_Set_Events, 
Par_Val_Trigger, 
3, 
awt, 
SYSPLUS_01, 
Ed_Set_Events, 
Ed_Set_Events, 
0, 
10 
 
 
This command is used by first writing the parameter data event_list and then triggering the command by writing the number of events 
to Data_Array_Name at Data_Array_Offset. 
 
Note: Only consecutive events can be set ( eg. to set event9, all 10 events must be set and 10 written to Data_Array_Name ). 
 
Parameter data setup:  (Use a value of 1 for “on” or a value of 0 for “off” per event) 
Offset from par_data_array_offset  Description 
Event0  
.. 
.. 
Event9 
 
4.4.87. 
Map Descriptor Example 83 - edit set auxs = aux_list 
//    Client Side Mao Descriptors 
 
 
 
 
 
 
 
 
 
Map Descriptor 
 
 
 
 
 
 
 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function,   Node_Name, 
SysPlus_Cmd, 
Par_Data_Array_Name, 
Par_Data_Array_Offset, 
Length 
Ed_Set_Auxs, 
Par_Val_Trigger, 
4, 
awt, 
SYSPLUS_01, 
Ed_Set_Auxs, 
Ed_Set_Auxs, 
0, 
10 
 
This command is used by first writing the parameter data aux_list and then triggering the command by writing the number of auxs to 
Data_Array_Name at Data_Array_Offset.  Note: Only consecutive auxs can be set ( eg. to set aux1, all auxs from 0 to 1 must be set 
and 2 written to Data_Array_Name ). 
 
Parameter data setup:  (Use a value of 1 for “on” or a value of 0 for “off” per aux) 
Offset from par_data_array_offset  Description 
Aux0  
.. 
.. 