FieldServer FS-8700-88 Manuale Utente

Pagina di 49
FS-8700-88 Envirotronics SystemsPlus   
 
 
 
 
Page 9 of 49 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
4.2. 
Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is connected 
to the FieldServer 
P1-P8
1
 
Protocol 
Specify protocol used 
SystemsPlus 
Baud* 
Specify baud rate 
300 – 19200, standard baud 
rates only 
Parity* 
Specify parity 
Even, Odd, None 
Data_Bits* 
Specify data bits 
7, 8 
Stop_Bits* 
Specify stop bits 
1, 2 
Handshaking*  Specify hardware handshaking 
RTS, RTS/CTS, None 
Poll _Delay* 
Time between internal polls 
0-32000 seconds, 1 second 
 
Example 
 
//    Client Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Handshaking, 
Poll_Delay 
P1, 
SystemsPlus, 
19200, 
None, 
None, 
0.100s 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric 
characters 
Protocol 
Specify protocol used 
SystemsPlus 
Port 
Specify which port the device is 
connected to the FieldServer 
P1-P8
1
 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Protocol, 
Port 
 
SYSPLUS_01, 
SystemsPlus, 
P1 
 
 
 
 
                                                
1
 
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction 
manual for details of the ports available on specific hardware.