Appendix A.5. Activating and De-activating Entities
These examples demonstrate the methodology to activate or de-activate equipment on the MXL/XLS panel as per the SBT-FSI protocol specification. This
relates to the opcode Activate/Deactivate Entity 0x7b/0x7c.
relates to the opcode Activate/Deactivate Entity 0x7b/0x7c.
The configuration example in Section 4 can be modified as per the example below for Activating and De-activating Entities on the MXL Panel.
// Client Side Connections
//
Connections
Port
,Baud ,Parity ,Data_Bits ,Line_drive_on ,Line_drive_off ,Enhanced_Protocol ,Protocol ,System_Type
P1
,19200 ,Even ,7
,0.001
,0.001
,No
,Cerberus ,MXL
Map_Descriptors
Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Block_Offset ,Length ,Msg_Type
POLLER_1
POLLER_1
,2.0s
,Counts_1
,0
,Rdbc
,Panel1
,1
,0
,19
,Poller
// this is for activation and deactivation of pseudo points
PNL_1_Act_Entity
,0s
,Act_Ent
,0
,Awt
,Panel1
,1
,1
,10
,Entity_Activate_Deact
The configuration example in Section 4 can be modified as per the example below for Activating and De-activating Entities on the XLS panel.
// Client Side Connections
//
Connections
Port
,Baud ,Parity ,Data_Bits ,Line_drive_on ,Line_drive_off ,Enhanced_Protocol ,Protocol ,System_Type
P1
,19200 ,Even ,7
,0.001
,0.001
,Yes
,Cerberus ,XLS
Map_Descriptors
Map_Descriptor_Name ,Scan_Interval ,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Block_Number ,Sub_Module ,Block_Offset ,Length ,Msg_Type
POLLER_1
POLLER_1
,2.0s
,Counts_1
,0
,Rdbc
,Panel1
,1
,-
,0
,19
,Poller
// this is for activation and deactivation of pseudo points
PNL_1_Act_Entity
PNL_1_Act_Entity
,0s
,Act_Ent
,0
,Awt
,Panel1
,1
,1
,1
,10
,Entity_Activate_Deact