CONFIGURING THE FIELDSERVER AS A SBT-FSI CLIENT 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual.  The 
information that follows describes how to expand upon the factory defaults provided in the configuration files 
included with the FieldServer (See “.csv” sample files provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer to communicate 
with a SBT-FSI Server. 
In FSI mode, the NIM-1R or NIM-1W or RPM allows the FieldServer to gather data from up to 63 MXL/XLS Panels 
connected via an MXL/XLS network.  The default configuration shipped with  the FieldServer will monitor two 
panels (1 and 2) with 8 modules (1 to 8) each.   
When the FieldServer is configured as a Client, two sets of data are collected by a “poller” Map Descriptor.   
The first is a collection of 19 counters per panel.  Each 16-bit counter is incremented by the poller Map Descriptor 
whenever the corresponding event occurs.  An external Client can read these counters to quickly determine 
whether a new event has been reported to the Server.  The counters are mapped into the Data Array specified for 
the poller Map Descriptor. Counter offsets into the Data Array per event type are indicated below: 
Event 
Counter Offset 
Fire Alarm In 
Fire Alarm Out 
Fire Alarm Acknowledge 
Trouble In 
Trouble Out 
Trouble Acknowledge 
Supervisory In 
Supervisory Out 
Supervisory Acknowledge 
Security Alarm In 
Event 
Counter Offset 
Security Alarm Out 
10 
Security Alarm Acknowledge  11 
Status In 
12 
Status Out 
13 
Test In 
14 
Test Out 
15 
Audible Silenced 
16 
Audible Unsilenced 
17 
System Reset 
18 
 
The second set of data is a collection of bit maps that can be queried to identify the device that has reported the 
event.  When an alarm event arrives from a device, the corresponding bit is set in two separate arrays.  The bit in 
one array indicates the alarm has occurred, and the bit in the other array indicates that the alarm has not yet been 
acknowledged.  When an “alarm clear” event arrives, the bit in the alarm array is cleared.  If an “alarm 
acknowledge” event arrives, the bit in the un-acknowledged array is cleared.  All event arrays in a Client driver 
configuration are optional.  To enable an event array, a Map Descriptor must be defined in the configuration using 
a Map Descriptor message type that corresponds to the array as shown in the following table: 
Array  
Msg_Type 
Fire Alarm  
Fire 
Fire Alarm Un-Acknowledged 
Fire_Ack 
Trouble Alarm 
Trouble 
Trouble Un-Acknowledged 
Trouble_Ack 
Supervisory Alarm 
Super 
Supervisory Un-Acknowledge 
Super_Ack 
Array  
Msg_Type 
Security Alarm 
Secur 
Security Alarm Un-Acknowledged  Secur_Ack 
Status  
Status 
Test 
Test 
Audible (Un)Silenced 
Audible 
System Reset 
Reset