FieldServer FS-8700-40 Manuale Utente

Pagina di 29
FS-8700-40 SBT FSI Driver Manual   
 
 
 
 
 
 
Page 9 of 29 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
4.2  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is connected to the FieldServer 
P1-P8, R1-R2
 
Protocol 
Specify protocol used 
Cerberus, 
SBT-FSI 
Enhanced_Protocol 
Enables legacy or enhanced protocol.. MXL panels do not currently 
support Enhanced_Protocol, so this parameter must be set to  “No” for 
MXL.  The parameter is normally set to “Yes” for XLS, but may be set to 
“No” if problems are being experienced. 
Yes (XLS) 
No (MXL) 
System_Type 
Specifies Siemens Panel type 
MXL, XLS 
Block_Acks
Specifies if the driver uses block or individual command acks 
 
Yes, No 
Fire_Alarms_Hold 
Specifies if the driver should hold fire alarms until the system reset, or 
clear on fire alarms going out 
Yes, No 
Baud* 
Specify baud rate 
19200 
(Vendor 
limitation) 
Parity* 
Specify parity 
Even  (Vendor 
limitation) 
Data_Bits* 
Specify data bits 
7 
(Vendor 
limitation) 
Stop_Bits* 
Specify stop bits 
1 
(Vendor 
limitation) 
Handshaking
Specify hardware handshaking 
None 
Poll _Delay* 
Time between internal polls 
0-32000 
seconds, 
second 
 
Example 
//    Client Side Connections 
Connections 
Port  ,Protocol  ,Baud 
,Parity  ,Data_Bits  ,Poll_Delay 
P1 
,SBT-FSI 
,19200  ,Even 
,7 
,0.100s 
 
                                                                 
5
 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available 
on specific hardware. 
6
 Refer to the Advanced Driver Manual for usage. This function not enabled on standard driver. 
7
 Handshaking is not supported.