Appendix C. EST3 Data Format:
Appendix C.1.
Input data format
Each input device is associated with a 16-bit value. The contents of the 16 bits are used to generate
status types as shown in the table below. Each incoming event is allocated to a status type
depending on its device type as shown in the table. It is possible to override this default status type
allocation. Refer to Appendix A.5 for more information.
status types as shown in the table below. Each incoming event is allocated to a status type
depending on its device type as shown in the table. It is possible to override this default status type
allocation. Refer to Appendix A.5 for more information.
Type
Encode
Value
Alarm Trouble Supervisory Monitor Others
Smoke
0
Y
Pull
1
Y
Heat
2
Y
Waterflow
3
Y
Stageone
4
Y
Zone
5
Y
AlarmVerify
6
Y
PreAlarm
7
Y
Security
8
Y
Station
9
Y
Emergency
10
Y
Supervisory
11
Y
Valve
12
Y
GateValve
13
Y
Tamper
14
Y
Temperature
15
Y
Power
16
Y
Signal
17
Y
TroubleOpen
18
Y
TroubleShort
19
Y
LocalTrouble
20
Y
MaintAlert
21
Y
DirtyHead
22
Y
DeviceComm
23
Y
GroundFault
24
Y
InternalTrouble
25
Y
BadType
26
Y
BadPersonality
27
Y
UnexpectedDevice
28
Y
CommonTrouble
29
Y
RelayConfirmation
30
Y
Monitor
31
Y
LocalMonitor
32
Y
Damper
33
Y
Fan
34
Y
Door
35
Y
Switch
36
Y
FirePhone
37
Y