FieldServer FS-8700-39 Manuale Utente

Pagina di 21
FS-8700-39 EST3 Driver Manual 
 
 
 
 
 
 
Page 3 of 21 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
1. 
EST3 Description  
The  EST3  External  Communications  Protocol  (ECP)  driver  allows  the  FieldServer  to  transfer  data  to 
and  from  EST  devices  over  RS-232  or  RS-485  (with  converter)  serial  ports  using  the  EST3  ECP 
protocol.  In the EST application the FieldServer always emulates a Client. 
 
The FieldServer makes use of the following ECP Services: 
 
Read Operations: 
• 
Report Service 
• 
Delta Service 
Write Operations: 
• 
Command Service 
 
All read  points are continually updated  using the  Report Service; response times are enhanced  using 
Delta Service broadcasts by the EST3 panel. 
 
The  information  that  follows  describes  how  to  expand  upon  the  factory  defaults  provided  in  the 
configuration files included with the FieldServer. 
 
 
 
2. 
Driver Scope of Supply 
2.1. 
Supplied By FieldServer Technologies for this Driver 
FIELDSERVER 
TECHNOLOGIES PART # 
DESCRIPTION 
FS-8915-10 
7’ Patch Cable 
FS-8917-03 
RJ45 to DB9M Connector adapter 
FS-8917-10 
DB9F to terminal Adapter 
FS-8700-39 
EST3 ECP Driver Manual 
 
2.2. 
Provided By the Supplier of 3
rd
 Party Equipment 
2.2.1. 
Hardware 
PART # 
DESCRIPTION 
VERSION 
 
EST3 Gateway 
 
 
2.2.2. 
Required 3
rd
 Party Configuration 
The  EST3  panel  has  to  be  set  into  the  “Gateway  Mode”  using  the  EST3  Configuration  tool  (3-
SDU) 
 
Possible Protocols 
 
ECP Type II 
Supported 
ECP Type II with Text 
Not Supported 
ECP Type III 
Supported 
ECP Type III with Text 
Not Supported