FieldServer FS-8700-39 Manuale Utente

Pagina di 21
FS-8700-39 EST3 Driver Manual 
 
 
 
 
 
 
Page 7 of 21 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
4.4. 
Client Side Map Descriptors 
4.4.1. 
FieldServer Related Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Map_Descriptor_Name  Name of this Map Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array where data 
is to be stored in the FieldServer 
One of the Data Array names 
from “Data Array” section above 
Data_Array_Offset 
Starting location in Data Array 
0 to maximum specified in “Data 
Array” section above 
Function 
Function of Client Map Descriptor  RDBC, WRBC
3
, WRBX 
4.4.2. 
Driver Related Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name of Node to fetch data from 
One of the node names 
specified in “Client Node 
Descriptor” above 
EST_Panel 
Panel 
0 - 63 
EST_Card 
Card 
0 - 255 
Address 
Starting address of read block 
0 - 1023 
Length 
Length of Map Descriptor 
For Reads: 1 to 34   For Writes: 
EST_Object_Type 
Object type parameter 
Relay, Led, ServGroup, 
GuardPtrl, ChkInGrp, 
AltMessage, Reset, PanelSil, 
AlarmSil, Drill, GAInhibit, 
Reboot, Evacuate, AltSensitiv, 
Partition, CmdList, Input, Zone, 
Card, AndGroup, Matrix, 
TimeCtrl, InstructionText, 
AmpPower, AudMsg, CmdList, 
MCmsg, SetDate, SetTime 
EST_Index 
Index parameter 
0 - 65535 
EST_Route 
Route parameter 
0 - 255 
EST_Priority 
Pri parameter 
0 - 4 (see note below)  
EST_Chan 
Chan parameter 
0 - 255 
EST_Msg_Index 
MsgIndex parameter 
0 - 65535 
EST_Account 
Account parameter 
0 - 255 
EST_ConfCL 
ConfCL parameter 
0 - 65535 
EST_Panel_Mask_1 
PanelMask(1) parameter (LSB) 
0 - 255 
EST_Panel_Mask_2 
PanelMask(2) parameter 
0 - 255 
EST_Panel_Mask_3 
PanelMask(3) parameter 
0 - 255 
EST_Panel_Mask_4 
PanelMask(4) parameter 
0 - 255 
EST_Panel_Mask_5 
PanelMask(5) parameter 
0 - 255 
EST_Panel_Mask_6 
PanelMask(6) parameter 
0 - 255 
EST_Panel_Mask_7 
PanelMask(7) parameter 
0 - 255 
EST_Panel_Mask_8 
PanelMask(8) parameter (MSB) 
0 - 255 
Data_Array_Low_Scale* 
Scaling zero in Data Array 
-32767 to 32767, 0 
Data_Array_High_Scale*  Scaling max in Data Array 
-32767 to 32767, 100 
Node_Low_Scale* 
Scaling zero in Connected Node 
-32767 to 32767, 0 
Node_High_Scale* 
Scaling max in Connected Node 
-32767 to 32767, 100 
                                                 
3
 WRBC is not recommended, as startup values may be invalid