FS-8704-13 GE-SRTP
Driver Manual
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 8
4.4.5 Map Descriptor Example 2 – Simple Write
This example writes data from the Fieldserver data array called DA_AO to the PLC identified as NODE1. The write is repeated every 5 seconds. Ten word
values are written to the PLC’s %AQ Data Table starting at location 20.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Scan_Interval, node_name, Address, Length, Data_Type
Write_AO , DA_AO , 0 , wrbc , 5.0s , Node1 , 20 , 10 , %AQ
Write
continuously
continuously
Write to the %AQ
(Analog Output)
table in the PLC.
(Analog Output)
table in the PLC.
Write to PLC
Table element
number 20 to 29
inclusive (10
elements)
Table element
number 20 to 29
inclusive (10
elements)