FieldServer FS-8700-82 Manuale Utente

Pagina di 31
FS-8700-82 Carrier DataLink 
 
 
 
 
 
 
Page 3 of 31 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com 
1. 
Carrier DataLink Description  
The  Carrier  DataLink  driver  allows  the  FieldServer  to  transfer  data  to  and  from  devices  over 
either RS-232 or RS-485 using Carrier DataLink protocol.  The FieldServer can emulate either a 
Server or Client.  
 
The Carrier DataLink Serial Driver allows variables to be read and written in system elements 
connected to a Carrier Comfort Network communication bus.  Up to 15 system elements may be 
connected  to  a  DataLink  Device.    Display,  Occupancy,  Set  Point  Tables  and  Carrier  Comfort 
Network (CCN) variables may be read or written. 
 
The DataLink device provides a gateway to CCN devices.  This driver polls the DataLink device 
which in turn reads/writes data to the CCN devices. 
 
Carrier limits the number of CCN devices that can polled from a DataLink Device as well as the 
data  that  can  be  transferred  between  some  CCN  devices  and  the  DataLink  device.  For 
information on these limitations please consult the Carrier Corporation.  
 
The driver is an active client driver.  This means that it initiates read/write polls with the DataLink 
device which is expected to provide responses.  Server functionality is not intended to provide 
full emulation of DataLink Devices but can be extended on request. 
 
The driver is configured to allow data tables to be read from the CCN devices via the DataLink 
device.  As the tables typically contain more than one data element, the retrieved data is stored 
in a number of consecutive FieldServer data array locations in the FieldServer.  The individual 
values cannot be scaled before they are stored.  The driver can provide descriptions for each of 
the table values retrieved.  Descriptions are stored in ASCII in a separate data array.  
 
The driver can be configured to read a specific variable from a CNN device and store its value 
using optional scaling in a configurable location in a FieldServer data array.  
 
The driver  can  be  configured  to  write  a  value  (using optional  scaling) from  a  FieldServer  data 
array  to  a  specific  variable  in  a  CNN  device,  provided  that  the  variable  allows  its  value  to  be 
written. 
 
The driver has no advanced knowledge of the CCN devices and their data tables.  Therefore it 
cannot validate table names or variable names specified in the configuration file.  This means 
that  the  driver  handles  each  table  in a generic  way,  without  regard for  the particular  variables 
that constitute the tables. 
 
It is important that you understand the limitations and exclusions of this driver. Refer to Section 
5.4 for more information.