Page 12 of 15 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Appendix B.  Driver Notes 
Appendix B.1. 
Setting the FieldServer’s DeviceNet MAC ID and Baudrate 
The  MAC  ID  and  Baudrate  can  be  set  in  the  FieldServer’s  CSV  file  using  the 
System_Station_Address and DNet_Master_Baudrate parameters or it can be set with DIP switches 
as depicted below.   
Note: 
The  System_Station_Address  parameter  must  be  removed  from  the  configuration  file  if  the  DIP 
switch setting is to be used. 
If System_Station_Address has not been defined in the CSV file, the DIP switch value for both MacID 
and Baudrate will be used and the baud parameter in the CSV file will be ignored. 
 
 
 
Appendix B.2. 
Using the Command and Status Data Arrays 
The Command Data Array controls the Scanner’s mode which can be either Run or Idle. The Scanner 
can  only  be  configured  when  in  Idle  mode.    A  non-zero  value  at  offset  zero  in  the  Command  Data 
Array  will  place  the  Scanner  in  Run  mode;  a  value  of  zero  will  place  it  in  Idle  mode.    The  Scanner