Message 
Description 
MET1:#13  Err.  Node=%d  cant  be 
selected  because  not  defined  in 
config. 
The  reported  device  could  not  be  selected  because  there 
isnt  a  node  descriptor  whose  Node_ID  matches  the 
reported device.
4
 
"Met1:#14 
FYI 
Poll_Delay 
overridden to %d 
The  driver  has  set  the  default  poll  delay  to  the  reported 
value.  This  setting  can  be  overridden  in  the  configuration 
file.
4
 
Met1:#15 Err. Set MD Length=%d 
The  driver  has  determined  that  the  Length  parameter  is 
too small. The reported length is the driver suggestion. 
4
 
Met1:#16 Err. Set MD Length 
The  parameter  called  Length  must  be  specified  for  each 
Map  Descriptor.  It  tells  the  FieldServer  how  much  Data 
Array  space  to  reserve.    Review  the  Map  Descriptor 
examples in this manual. 
4
 
MET1:#17  Err.  MD  too  long, 
Max=%u 
Review the Map Descriptor examples in this manual. 
4
 
MET1:#18  Err.  Invalid  Port=%d. 
Valid Range=0-63 
Invalid entry for port.
4
 
MET1:#19 
Err. 
Invalid 
SubDevice=%d.  Valid  Range=1-
64 
Invalis entry for SubDevice
4
 
MET1:#20  Err.  Met1_Function  not 
specified 
MET1:#21 
Err. 
Met1_Function='%s' 
not 
recognized 
The  parameter  “Met1_Function’  must  be  specified  for 
every  Map  Descriptor.  Refer  to  Section  4.4.2  as  well  as 
Map Descriptor examples provided in Chapter 4.
4
 
 
 
Appendix A.1.  Driver Operating and Error Statistics 
These notes outline any driver specific use of the normal driver operating stats documented 
in the FieldServer Configuration Manual. 
 
•  Timeouts  :  During  normal  polling,  a  timeout  can  mean  that  the  field  device  did  not 
respond to the select message, (or the sub-device select message) or did not respond to 
the poll for data or the command poll. 
•  Exception  Stats:  If  the  driver  select  a  device  ,  sub-device  or  port  and  the  return  code 
from the device is unexpected the this stat is incrmented by 1. 
•  Ignored  Stats:  If  the  current  record  is  read  and  there  is  more  data  than  can  be  stored 
than specified by the Length of the Map Descritor then this stat is incremented. 
•  The driver does not use the normal operating stats to count message and bytes received 
in response to select / sub select messages. 
 
                                                 
4
 
Update the configuration file, download the modified configuration file and reset the FieldServer for the 
changes to take effect