Appendix A.2.1. 
Sim4100_Card Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
values are valid for Simplex devices.  Refer to Note (1). 
 
Many  commands  and  output  message  contain  system  point  ID  fields.    These  fields 
reflect the way a 4100 point (local, external, real, pseudo), is referred to.   
 
There  are  two  basic  formats  allowed,  address  format  <apoint>,  and  symbolic  format 
<spoint>.   
 
In the Simplex device the terminal ADDRESS flag is set (DEFAULT) so that <apoint> is 
always  used  in  computer  messages;  otherwise,  the  symbolic  form  is  used.    The 
FieldServer cannot work with symbolic (spoint) addresses. 
 
Appendix A.2.2. 
<apoint> 
Format <card>-<point>-<sub> 
Legend: 
 
<card> 
4100 card, pseudos included, See note (1) 
<point> 
4100 point (sometimes slot), See note (2) 
<sub> 
4100 sub-point (sometime point), See note (2) 
Examples: 
 
0-6-6 
Master trouble point (LCD trouble) 
5-0-1 
Typical card status point, card at address 5 
3-1-0 
Point 1 for card at address 3 
 
Notes: 
(1) 
The following ranges are valid for Simplex Devices: 
 
 
Card address  Card type 
0-119 
Physical (Hardware) cards 
128-143 
Digital Pseudo cards 
144-159 
Analog Pseudo cards 
160-175 
List Pseudo cards 
 
 
(2) 
The  range  of  point  and  sub-point  fields  for  point  addressing  is  very  sparse  and 
depends on the type of card at that location.  Contact Simplex Time Company for details 
on point address ranges for specific cards. 
Appendix A.2.3. 
Sim4100_Point Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
the  values  are  valid  for  Simplex  devices  -  see  Sections  6.3  and  6.4  for  further 
information.  
Appendix A.2.4. 
Sim4100_sub Keyword 
The FieldServer will accept any positive integer number including zero; however, not all 
the  values  are  valid  for  Simplex  devices  -  see  Sections  6.3  and  6.4  for  further 
information.