FieldServer FS-8700-41 Manuale Utente

Pagina di 58
FS-8700-41 Simplex 4100 Driver Manual   
 
 
 
 
Page 4 of 58 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-2296   Toll_Free: 888-509-1970   email: support@fieldserver.com 
1. 
Simplex Time Recorder Company - 4100 Computer Port Protocol 
The  Simplex  Time  Recorder  Company  -  4100  Computer  Port  Protocol  driver  allows  the 
FieldServer  to  transfer  data  to  and from  devices  over  either  RS-232  or RS-485  using  Simplex 
Time Recorder Company - 4100 Computer Port Protocol.   
 
This  driver  is  designed  to  connect  to  a  Simplex  4100  panel  equipped  to  support  the  “4100 
Computer  Port  Protocol”  as  defined  in  Simplex’s  document  950-004  Revision  E  dated  28  July 
2000.    The  implementation  provides  a  selected  subset  of  protocol  functions  and  subset  of 
functionality  for  each  of  these  selected  functions.    It  is  important  to  note  the  exclusions  and 
limitations described in this document. 
 
The  driver  is  a  capable  of  parsing  and  storing  information  sent  by  a  panel  in  the  form  of 
unsolicited messages which are typically generated when there is a state change in the panel or 
one of the connected devices.  The driver is also capable of polling for point and panel status 
data and some additional data such as the panel’s time and revision information.  In addition the 
driver  is  capable  of  setting  some  control  points  in  the  panel  –  acknowledging  and  resetting 
alarms and writing data (where permitted) to some analog and discrete points. 
 
This is a client only driver and is not capable of emulating a Simplex Panel.  Server emulation is 
provided for test purposes only and is not supported or documented. 
 
1.1. 
Supported Panel Types 
The driver has been tested against 4020, 4100 and 4100U panels. There is no difference in 
the protocol format between the various panels. What changes is the panel firmware version 
and with the firmware changes the supported function set changes. 
 
1.2. 
Simplex Panel Firmware Revision vs. Supported Functionality 
This driver was primarily tested against a 4020 panel with firmware revision 9.2. Beta testing 
against a 4100 panel with a firmware revision 10.x was also performed. 
 
A  grid  of  firmware  revision  number  and  supported  functions  is  provided  by  Simplex.    This 
grid is available from Simplex.  Request the ‘CPP Revision Compatibility’ Table. 
 
All the functions described in this manual are supported for firmware revisions 10 or higher.  
For revisions between 9.2 and 10, the ‘Earths’ and ‘Value’ functions described in this driver 
are  not  supported  by  the  Simplex  Panels.    For  revisions  lower  than  9.2,  then  functions 
supported  need  to  be  determined  by  trial  and  error.    We  are  fairly  confident  that  all  the 
functions supported by version 9x are also supported by versions 8x of the panel firmware.