FieldServer FS-8700-132 Manuale Utente
FS-8700-132 Gamewell FCI-E3 Driver Manual
Page 13 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix A. Advanced Topics
Appendix A.1.
Events and Event Categories
The driver reports the event cause using the matching index value. There are 4 event categories:
1 = Other
2 = Fault
2 = Fault
3 = Alarm
4 = Trouble
4 = Trouble
The message category must match the ‘Event Type’ parameter specified on a Map Descriptor before
that Map Descriptor can be considered for storage of the message data.
Index
Category
Event
1
FCI_EVENT_TYPE_FAULT
"Fault"
2
FCI_EVENT_TYPE_OTHER "Short"
3
FCI_EVENT_TYPE_OTHER "Disconnect"
3
4
FCI_EVENT_TYPE_OTHER "Comm Fault"
5
FCI_EVENT_TYPE_OTHER "Config Err"
6
FCI_EVENT_TYPE_OTHER "Eeprom Bad"
7
FCI_EVENT_TYPE_OTHER "Reset"
8
FCI_EVENT_TYPE_OTHER "Silence"
9
FCI_EVENT_TYPE_OTHER "Cross Zone"
3
10
FCI_EVENT_TYPE_OTHER "Acknwldgd"
11
FCI_EVENT_TYPE_OTHER "Walk Test"
12
FCI_EVENT_TYPE_OTHER "Alarm Test"
13
FCI_EVENT_TYPE_OTHER "SPVSN Test"
14
FCI_EVENT_TYPE_OTHER "Fault Test"
15
FCI_EVENT_TYPE_OTHER "Fire Drill"
16
FCI_EVENT_TYPE_OTHER "Batt Test"
17
FCI_EVENT_TYPE_OTHER "PRGM Mode"
18
FCI_EVENT_TYPE_OTHER "Action"
19
FCI_EVENT_TYPE_OTHER "Loop Break"
20
FCI_EVENT_TYPE_ALARM "Alarm"
21
FCI_EVENT_TYPE_OTHER "P.A.S."
22
FCI_EVENT_TYPE_OTHER "Off-Normal"
23
FCI_EVENT_TYPE_OTHER "RZA Fault"
3
24
FCI_EVENT_TYPE_OTHER "Verify"
3
25
FCI_EVENT_TYPE_OTHER "CM Short"
3
26
FCI_EVENT_TYPE_OTHER "Test Fail"
27
FCI_EVENT_TYPE_OTHER "Alert"
28
FCI_EVENT_TYPE_OTHER "Dirty"
29
FCI_EVENT_TYPE_OTHER "Very Dirty"
30
FCI_EVENT_TYPE_OTHER "Missing"
31
FCI_EVENT_TYPE_OTHER "Wrong Type"
32
FCI_EVENT_TYPE_OTHER "Extra Addr"
33
FCI_EVENT_TYPE_OTHER "Clock Err"
3
34
FCI_EVENT_TYPE_TRBLE
"Trouble"
3
35
FCI_EVENT_TYPE_OTHER "MLT Events"
3
36
FCI_EVENT_TYPE_OTHER "Alrm Ackd"
37
FCI_EVENT_TYPE_OTHER "Outpt Fail"
38
FCI_EVENT_TYPE_OTHER "Tally Flt"
39
FCI_EVENT_TYPE_OTHER "AC Flt To"
40
FCI_EVENT_TYPE_OTHER "Trbl Ackd"
41
FCI_EVENT_TYPE_OTHER "Access"
42
FCI_EVENT_TYPE_OTHER "Netwrk Flt"
43
FCI_EVENT_TYPE_OTHER "NetGndFlt"
44
FCI_EVENT_TYPE_OTHER "Dact Fault"
45
FCI_EVENT_TYPE_OTHER "Node Msng"
46
FCI_EVENT_TYPE_OTHER "Node Xtra"
47
FCI_EVENT_TYPE_OTHER "Fans Off"
48
FCI_EVENT_TYPE_OTHER "Xzone Alrm"
3
Not defined in the spec