Events and Event Categories 
The driver reports the event cause using the matching index value.  There are 4 event categories: 
1 = Other 
2 = Fault 
3 = Alarm 
4 = Trouble 
 
The message category must match the ‘Event Type’ parameter specified on a Map Descriptor before 
that Map Descriptor can be considered for storage of the message data. 
Index 
Category 
Event 
FCI_EVENT_TYPE_FAULT  
"Fault" 
FCI_EVENT_TYPE_OTHER   "Short" 
FCI_EVENT_TYPE_OTHER   "Disconnect"
3
 
FCI_EVENT_TYPE_OTHER   "Comm Fault" 
FCI_EVENT_TYPE_OTHER   "Config Err" 
FCI_EVENT_TYPE_OTHER   "Eeprom Bad" 
FCI_EVENT_TYPE_OTHER   "Reset" 
FCI_EVENT_TYPE_OTHER   "Silence" 
FCI_EVENT_TYPE_OTHER   "Cross Zone"
3
 
10 
FCI_EVENT_TYPE_OTHER   "Acknwldgd" 
11 
FCI_EVENT_TYPE_OTHER   "Walk Test"  
12 
FCI_EVENT_TYPE_OTHER   "Alarm Test" 
13 
FCI_EVENT_TYPE_OTHER   "SPVSN Test" 
14 
FCI_EVENT_TYPE_OTHER   "Fault Test" 
15 
FCI_EVENT_TYPE_OTHER   "Fire Drill" 
16 
FCI_EVENT_TYPE_OTHER   "Batt Test" 
17 
FCI_EVENT_TYPE_OTHER   "PRGM Mode" 
18 
FCI_EVENT_TYPE_OTHER   "Action" 
19 
FCI_EVENT_TYPE_OTHER   "Loop Break" 
20 
FCI_EVENT_TYPE_ALARM   "Alarm" 
21 
FCI_EVENT_TYPE_OTHER   "P.A.S." 
22 
FCI_EVENT_TYPE_OTHER   "Off-Normal" 
23 
FCI_EVENT_TYPE_OTHER   "RZA Fault"
3
 
24 
FCI_EVENT_TYPE_OTHER   "Verify"
3
 
25 
FCI_EVENT_TYPE_OTHER   "CM Short"
3
 
26 
FCI_EVENT_TYPE_OTHER   "Test Fail" 
27 
FCI_EVENT_TYPE_OTHER   "Alert" 
28 
FCI_EVENT_TYPE_OTHER   "Dirty" 
29 
FCI_EVENT_TYPE_OTHER   "Very Dirty" 
30 
FCI_EVENT_TYPE_OTHER   "Missing" 
31 
FCI_EVENT_TYPE_OTHER   "Wrong Type" 
32 
FCI_EVENT_TYPE_OTHER   "Extra Addr"  
33 
FCI_EVENT_TYPE_OTHER   "Clock Err"
3
 
34 
FCI_EVENT_TYPE_TRBLE  
"Trouble"
3
 
35 
FCI_EVENT_TYPE_OTHER   "MLT Events"
3
 
36 
FCI_EVENT_TYPE_OTHER   "Alrm Ackd" 
37 
FCI_EVENT_TYPE_OTHER   "Outpt Fail" 
38 
FCI_EVENT_TYPE_OTHER   "Tally Flt" 
39 
FCI_EVENT_TYPE_OTHER   "AC Flt To" 
40 
FCI_EVENT_TYPE_OTHER   "Trbl Ackd" 
41 
FCI_EVENT_TYPE_OTHER   "Access" 
42 
FCI_EVENT_TYPE_OTHER   "Netwrk Flt" 
43 
FCI_EVENT_TYPE_OTHER   "NetGndFlt" 
44 
FCI_EVENT_TYPE_OTHER   "Dact Fault" 
45 
FCI_EVENT_TYPE_OTHER   "Node Msng" 
46 
FCI_EVENT_TYPE_OTHER   "Node Xtra" 
47 
FCI_EVENT_TYPE_OTHER   "Fans Off" 
48 
FCI_EVENT_TYPE_OTHER   "Xzone Alrm" 
                                                 
3
 
Not defined in the spec