Example 
 
//    Data Arrays 
 
 
 
 
 
Data_Arrays 
 
 
Data_Array_Name, 
Data_Array_Format, 
Data_Array_Length 
Byte_Output, 
Byte, 
10 
Byte_Input, 
Byte, 
10 
Word_Output, 
Uint16, 
10 
Word_Input, 
Uint16, 
10 
Float_Output, 
Float, 
10 
Float_Input, 
Float, 
10 
 
 
 
4.3. 
Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Adapter Adapter 
Name  Prof_DP 
 
Example 
 
//    Client Side Connections
 
 
 
 
Connections
 
 
Adapter 
 
Prof_DP 
 
 
 
4.4. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for node 
Up to 32 alphanumeric characters 
Node_ID 
Station address of physical 
remote Profibus Slave 
0-125 
Protocol 
Specify protocol used 
Anybus_Prof_DP_M 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Node_ID, 
Protocol 
 
PDP_SLV003, 
3, 
Anybus_Prof_DP_M   
PDP_SLV125, 
125, 
Anybus_Prof_DP_M